Troubleshooting
Samsung Electronics 4-95
4-4-51 EVI In Temperature sensor error (Open/Short)
(Operation) ×(Reservation) (Blast) ×(Filter) ×(Defrost)
Disconnection or breakdown of relevant sensor .
Refer to the judgment method below.
Indoorunit display
Judgment Method
Cause of problem
Outdoor unit display
1.
Cause of problem
Did the connector for the EVI In
Temperature sensor break away from
the PCB?
Did the resistance value
significantly stray from the following
temperature table?
Separate the connector of
the Outdoor EVI In
Temperature sensor from the PCB and measure
the resistance value between the 2 terminals.
Restart operation after replace the PCB
Restart operation after connecting
the connector to PCB
R
eplace this part as it is the defective of the
Outdoor EVI In Temperature sensor itself.
No
No
Yes
Yes
Temperature(°C)
70
60
50
40
30
20
10
0
-10
Resistance(K)
2.2
3.0
4.2
5.8
8.3
12.1
18.0
27.3
43.0
 
EVI-IN
EVI-IN

Table of Contents

Other manuals for Samsung AM160FNBFEB/EU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samsung AM160FNBFEB/EU and is the answer not in the manual?

Samsung AM160FNBFEB/EU Specifications

General IconGeneral
TypeAir conditioner indoor unit
Multi-split-
Product colorWhite
Gas hose diameter15.88 mm
Liquid hose diameter9.52 mm
Refrigerating mediumR410A
Air conditioner functionsHeating
Heating capacity (nominal)54600 BTU/h
Heating capacity in watts (max)16000 W
Cooling capacity in watts (nominal)- W
Operating temperature (heating) (T-T)-20 - 24 °C
AC input voltage220-240 V
Current (heating)14.3 A
AC input frequency50-60 Hz
Design load (cooling)- kW
Energy efficiency scaleA++ to G
Power consumption (heating) (max)3100 W
Hourly energy consumption (cooling)- kWh
Energy efficiency class (heating) (Average heating season)A++
Indoor unit typeWall-mountable
Indoor unit depth330 mm
Indoor unit width518 mm
Indoor unit height1210 mm
Indoor unit weight104000 g
Indoor units quantity1
Indoor unit package depth426 mm
Indoor unit package width652 mm
Indoor unit package height1289 mm
Indoor unit package weight107000 g
Indoor unit sound power level42 dB
Indoor unit noise level (high speed)60 dB
Outdoor unit noise level- dB