Troubleshooting
4-128 Samsung Electronics
4-4-85 Breakdown of an EEV(1
st
)
1. How to diagnose
Detect only on cooling operation. (No detection during heating operation.)
During cooling operation, the temperature of the inlet or outlet ducts of heat exchanger
is kept lower than 0˚C for more than
20 minutes without cessation
2. How to check
1) Check if the wire of an electronic expansion valve is correctly connected to the PCB of indoor u
nit.
2) Check if the coil of an electronic expansion valve is correctly plugged into the main body.
3) Check if there is any rust on the surface of the coi
l of an electronic expansion valve with the naked eye, and then check the
resistance between each terminal to find any wire breaking or short circuit.
4) Press the RESET KEY (K3) o
f the outdoor unit then see if the same error occurs.
4) - In case of closure problem, operate the indoor unit in which the error has occurred.
4) - In case of opening problem, please do not operate the indoor unit in which the error has occurred.
5) If there is no problem with the above checkup items, replace the el
ectronic expansion valve of the troubled indoor unit.
4) - As an electronic expansion valve replacement is tricky work that requires collecting refrigerants in all systems, please make sure
to check the above items be
fore replacement.

Table of Contents

Other manuals for Samsung AM160FNBFEB/EU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samsung AM160FNBFEB/EU and is the answer not in the manual?

Samsung AM160FNBFEB/EU Specifications

General IconGeneral
TypeAir conditioner indoor unit
Multi-split-
Product colorWhite
Gas hose diameter15.88 mm
Liquid hose diameter9.52 mm
Refrigerating mediumR410A
Air conditioner functionsHeating
Heating capacity (nominal)54600 BTU/h
Heating capacity in watts (max)16000 W
Cooling capacity in watts (nominal)- W
Operating temperature (heating) (T-T)-20 - 24 °C
AC input voltage220-240 V
Current (heating)14.3 A
AC input frequency50-60 Hz
Design load (cooling)- kW
Energy efficiency scaleA++ to G
Power consumption (heating) (max)3100 W
Hourly energy consumption (cooling)- kWh
Energy efficiency class (heating) (Average heating season)A++
Indoor unit typeWall-mountable
Indoor unit depth330 mm
Indoor unit width518 mm
Indoor unit height1210 mm
Indoor unit weight104000 g
Indoor units quantity1
Indoor unit package depth426 mm
Indoor unit package width652 mm
Indoor unit package height1289 mm
Indoor unit package weight107000 g
Indoor unit sound power level42 dB
Indoor unit noise level (high speed)60 dB
Outdoor unit noise level- dB

Related product manuals