160/301
Siemens Building Technologies Basic Documentation LMV5... CC1P7550en
HVAC Products 8 Commissioning instructions for the LMV5... system 13.08.2004
The burner control proceeds with the startup sequence until the ignition position (Phase
36) is reached. There, the burner control stops again for setting the ignition positions of
the actuators.
Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6
Params & Display
RatioControl
OilSettings
SpecialPositions
IgnitionPos
IgnitionPosOil
IgnitionPosAir
IgnitionPosAux
Aux2
Aux3
VSD
Only
LMV52...
To repeatedly verify the ignition positions, the program sequence can be stopped in in-
terval phase 44 or 52 (interval with ignited flame on completion of the respective safety
time).
When the program stop is deactivated, the burner proceeds with its program until normal
operation is reached (Phase 60).
If the switching points of the burner stages have not yet been defined, the ignition posi-
tions of the actuators will be used as the first stage for the moment.
24. Ignition positions