Certification
EMI and Environmental Type Tests 49
Test Description Test Levels
Severity
Levels
Signal ports +/- 4 kV Line-to-Earth,
+/- 2 kV Line-to-Line
4
DC Power Ports +/- 2 kV Line-to-Earth,
+/- 1 kV Line-to-Line
3
IEC 61000-4-5 Surge
AC Power Ports +/- 4 kV Line-to-Earth,
+/- 2 kV Line-to-Line
4
Signal ports
DC Power Ports
AC Power Ports
IEC 61000-4-6 Induced (Conducted) RFI
Earth ground ports
10 V 3
40 A/m, continuous,
1000 A/m for 1 s
Note
a
IEC 61000-4-8 Magnetic Field Enclosure Ports
1000 A/m for 1 s 5
DC Power Ports 30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
IEC 61000-4-29 Voltage Dips and Interrupts
AC Power Ports 30% for 1 period, 60% for 50 periods
IEC 61000-4-11 Voltage Dips and Interrupts AC Power Ports 100% for 5 periods,
100% for 50 periods
Signal ports
DC Power Ports
IEC 61000-4-12 Damped Oscillatory
AC Power Ports
2.5 kV common, 1 kV
differential mode @1 MHz
3
Signal portsIEC 61000-4-16 Mains Frequency Voltage
DC Power Ports
30 V Continuous, 300 V for 1 s 4
IEC 61000-4-17 Ripple on DC Power Supply DC Power Ports 10% 3
Signal ports 2 kVAC (Failsafe Relay output)
DC Power Ports 1.5 kVDC
Dielectric Strength
AC Power Ports 2 kVAC
Signal ports 5 kV (Failsafe Relay output)
DC Power Ports
IEC 60255-5
HV Impulse
AC Power Ports
5 kV
a
Siemens-specified severity levels
IEEE 1613 (C37.90.x) EMI Immunity Type Tests
NOTE
The RX1501 meets Class 2 requirements for an all-fiber configuration and Class 1 requirements for
copper ports.