50 EMI and Environmental Type Tests
Test Description Test Levels
Signal ports 5 kV (Failsafe Relay Output)
DC Power Ports
HV Impulse
AC Power Ports
5 kV
Signal ports 2 kVAC
DC Power Ports 1.5 kVDC
IEEE C37.90
Dielectric Strength
AC Power Ports 2 kVAC
Signal ports +/- 4 kV @ 2.5 kHz
DC Power Ports
AC Power Ports
Fast Transient
Earth ground ports
+/- 4 kV
Signal ports 2.5 kV common mode @1MHz
DC Power Ports
IEEE C37.90.1
Oscillatory
AC Power Ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
IEEE C37.90.2 Radiated RFI Enclosure ports 35 V/m
Enclosure Contact +/-2 kV, +/-4 kV, +/- 8 kVIEEE C37.90.3 ESD
Enclosure Air +/-4 kV, +/-8 kV, +/-15 kV
Environmental Type Tests
Test Description Test Levels
IEC 60068-2-1 Cold Temperature Test Ad -40 °C (-40 °F), 16 Hours
IEC 60068-2-2 Dry Heat Test Bd 85 °C (185 °F), 16 Hours
IEC 60068-2-30 Humidity (Damp Heat, Cyclic) Test Db 95% (non-condensing), 55 °C (131 °F), 6 cycles
IEC 60255-21-1 Vibration Level 2 (2 g @ 10-150 Hz)
Shock Level 2 (30 g @ 11 mS)IEC 60255-21-2
Bump Level 1 (10 g @ 16 mS)
IEC 60255-21-3 Seismic Level 2 (Method A)
MIL-STD-810G Altitude 12192 m (40000 ft) @ 40 °C x 90 minutes
Long LifeIEC 61373
Shock
Category 1 Class B

Table of Contents

Other manuals for Siemens RUGGEDCOM RX1510

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens RUGGEDCOM RX1510 and is the answer not in the manual?

Siemens RUGGEDCOM RX1510 Specifications

General IconGeneral
BrandSiemens
ModelRUGGEDCOM RX1510
CategorySwitch
LanguageEnglish

Related product manuals