Configuring with Web Based Management
4.4 "System" menu
SCALANCE SC-600 Web Based Management (WBM)
208 Configuration Manual, 10/2021, C79000-G8976-C475-03
4.4.15 Fault monitoring
4.4.15.1 Power supply
Settings for monitoring the power supply
Configure whether or not the power supply should be monitored by the messaging
system. With a redundant power supply, configure the monitoring separately for each
individual feed-in line.
A fault is then signaled by the message system when there is no power on one of the
monitored lines (line 1 or line 2) or when the voltage is too low.
Note
You will find the permitted operating voltage limits in the compact operating instructions
of the device.
A fault causes the signaling contact to trigger and the fault LED on the device to light up
and, depending on the configuration, can trigger a trap or an entry in the event log table.
Procedure
1. Click the check box in front of the line name you want to monitor to enable or disable
the monitoring function.
2. Click the "Set Values" button.

Table of Contents

Other manuals for Siemens SIMATIC NET SCALANCE SC-600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET SCALANCE SC-600 and is the answer not in the manual?

Siemens SIMATIC NET SCALANCE SC-600 Specifications

General IconGeneral
Product SeriesSC-600
VLAN SupportYes
VLAN standardIEEE 802.1Q
QoS SupportYes
Type of housingMetal
Product FamilySCALANCE
Product type designationSCALANCE SC-600
Port TypesEthernet
Number of 100/1000Base-SFP ports2
Operating Temperature-40°C to +60°C
Ambient temperature during operation-40 ... 60 °C
Ambient temperature during storage-40 ... 70 °C
Relative humidity during operation10% to 95% (non-condensing)
Protection class IPIP30
Power Supply24 V DC
Mounting TypeDIN rail
MTBFVaries by model
CertificationsCE, UL, cUL, ATEX, IECEx
Switching CapacityVaries by model
ThroughputVaries by model
MAC Address TableVaries by model
Number of VLANsVaries by model
Max. frame sizeVaries by model