Description of system components
8.3 Operator panel with display
SIMOCODE pro
112 System Manual, 05/2019, A5E40507475002A/RS-AD/004
8.3.3.3 Read and adapt main display
To enable users speedy viewing of the measured values typically shown on their
switchboard, various profiles are stored in the operator panel with display that enable user-
specific adaptation of the standard measured values displayed in the SIMOCODE pro main
display. The profile is selected in the menu "Display settings" Profiles (see Section Adapt
display settings (Page 126)).
The set current, the selected class time for the overload protection system and the use of
temperature monitoring based on thermistors or analog temperature sensors are displayed
(if programmed) at the bottom left of the main display. The submenus of the main display
can be navigated with the right-hand softkey. For motors with two speeds, the left-hand
softkey can be used to alternate between the display of the two set currents.
IL1, IL2, IL3 [A]
1)
Shows the currents in all three phases in A.
IL1, IL2, IL3 [%]
1)
Displays the currents in all three phases as a percentage of the set current.
Imax [A]
1)
Shows the maximum current of all three phases in A.
Imax [%]
1)
Displays the maximum current of all three phases as a percentage of the set current.
Imax, Cos phi
2)
Displays the maximum current of all three phases in amps and the power factor.
Imax, UL1-N, Cos phi, S
3)
Shows the maximum current of all three phases in amps, the phase voltage UL1 in V, the
power factor, and the apparent power in kVA.
Imax, UL1-L2, Cos phi, S
4)
Shows the maximum current of all three phases in A, the line-to-line voltage UL1-L2 in V, the
power factor, and the apparent power in kVA.
Imax, UL1-N, Cos phi, P
3)
Shows the maximum current of all three phases in amps, the phase voltage UL1 in V, the
power factor, and the active power in kW.
Imax, UL1-L2, Cos phi, P
4)
Shows the maximum current of all three phases in A, the line-to-line voltage UL1-L2 in V, the
power factor, and the active power in W.
In1/output AM1 / In1/output AM2
5)
[mA]
Shows the current value at input 1 of analog module 1 / 2 and at the output of analog module
1 / 2 in mA.
In2/output AM1 / In2/output AM2
5)
[mA]
Shows the current value at input 2 of analog module 1 / 2 and at the output of analog module
1 / 2 in mA.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro C and is the answer not in the manual?

Siemens SIMOCODE pro C Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro C
CategoryControl Unit
LanguageEnglish

Related product manuals