Description of system components
8.3 Operator panel with display
SIMOCODE pro
122 System Manual, 05/2019, A5E40507475002A/RS-AD/004
8.3.3.8 Displays the current status of all device I/Os
The "Device I/Os" menu item provides a complete overview of the current status of all inputs
and outputs of the basic unit as well as any connected expansion modules. The type of
status information displayed is directly dependent upon the SIMOCODE pro hardware
configuration.
These are the most important menus by way of example:
Basic unit
Inputs 1 (2, 3, 4)
Outputs 1 (2, 3)
PTC high resistance/not present
PTC ok, PTC short circuit
Current measurement
IL1, Il2, IL3: Displays the currents (in A) in all three phases (possible only if a current
measuring module or current / voltage measuring module is used).
Voltage measurement
UL1-N, UL2-N, UL3-N: Displays all line-to-line voltages in V (possible only if a current /
voltage measuring module is used and the OPD is version *E04* or higher and line-to-line
voltage is set/configured).
U L1-L2, U L2-L3, U L3-L1: Displays all line-to-line voltages in V (possible only if a
current / voltage measuring module is used, line-to-line voltage is set/configured and the
OPD used is version *E04* or higher).
Digital module 1, digital module 2
Inputs 1 (2, 3, 4): Inputs 1, 2, 3, 4 "monostable" or "bistable."
Outputs 1, 2 "monostable" (possible only if digital module 1 is used as "monostable").
Note
Display
For OPD up to product version *E03*, the display is different.
Outputs 1, 2 "bistable" (possible only if digital module 1 is used as "monostable" or
"bistable").
Digital module 1 as DM-F Local
Possible only if digital module 1 is "Local," an OPD as from version *E04* and a
SIMOCODE pro V (PB basic unit as from product version *E07*) is used.
Inputs DM-F Local: Inputs "IN," "Start," "Feedback circuit," "Cascaded."
Sensor channels DM-F Local: Sensor channels 1, 2
Outputs DM-F Local: Outputs 1, 2, "Enabling circuit."

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro C and is the answer not in the manual?

Siemens SIMOCODE pro C Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro C
CategoryControl Unit
LanguageEnglish

Related product manuals