Features
4
Multifunction, electronic full motor protection for rated motor currents up to 820 A
SIMOCODE pro provides comprehensive protection of the motor feeder by means of a
combination of delayable, multi-level protection and monitoring functions:
Current-dependent electronic overload protection (CLASS 5 to 40)
Thermistor motor protection
Phase failure/unbalance protection
Stalled rotor protection
Monitoring of adjustable limit values for the motor current
Voltage monitoring
Active power monitoring
Dry-running protection for centrifugal pumps by means of active power monitoring
Monitoring of cos phi (no-load operation/load shedding)
Ground-fault monitoring
Temperature monitoring, e.g. using Pt100/Pt1000
Monitoring of operating hours
Monitoring of downtimes
Monitoring the number of starts within a specific period of time
Safety-related tripping of motor feeders, e.g. fail-safe tripping in the process industry,
locally or via fieldbus (see manual "SIMOCODE pro Safety fail-safe digital modules"
(https://support.automation.siemens.com/WW/view/en/50564852
))
Recording of measured curves
SIMOCODE pro is able to record measured curves and can, for example, illustrate the
characteristic curve of the motor current during motor startup.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro C and is the answer not in the manual?

Siemens SIMOCODE pro C Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro C
CategoryControl Unit
LanguageEnglish

Related product manuals