Commissioning
5.6 Function commissioning
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167
83
Parameter Function Setting
P2182[0...2] Belt threshold frequency 1 [Hz] Range: 0.00 ... 599.00 (factory default: 5.00)
P2183[0...2] Belt threshold frequency 2 [Hz] Range: 0.00 ... 599.00 (factory default: 30.00)
P2184[0...2] Belt threshold frequency 3 [Hz] Range: 0.00 ... 599.00 (factory default: 30.00)
P2185[0...2] Upper torque threshold 1 [Nm] Range: 0.0 ... 99999.0 (factory default: value in r0333)
P2186[0...2] Lower torque threshold 1 [Nm] Range: 0.0 ... 99999.0 (factory default: 0.0)
P2187[0...2] Upper torque threshold 2 [Nm] Range: 0.0 ... 99999.0 (factory default: value in r0333)
P2188[0...2] Lower torque threshold 2 [Nm] Range: 0.0 ... 99999.0 (factory default: 0.0)
P2189[0...2] Upper torque threshold 3 [Nm] Range: 0.0 ... 99999.0 (factory default: value in r0333)
P2190[0...2] Lower torque threshold 3 [Nm] Range: 0.0 ... 99999.0 (factory default: 0.0)
P2192[0...2] Time delay for belt failure [s] Range: 0 ... 65 (factory default: 10)
5.6.3 Commissioning advanced functions
5.6.3.1 Starting the motor in super torque mode
Functionality
This startup mode applies a torque pulse for a given time to help start the motor.
Typical application field
Sticky pumps
Setting parameters
Parameter Function Setting
P3350[0...2] Super torque mode = 1: Enable super torque mode
Note: When the value of P3350 is changed, the value of P3353
is changed as follows:
P3350 = 2: P3353 = 0.0s
P3350 ≠ 2: P3353 = default
The ramp time of 0s gives an additional 'kicking' effect when
hammer start is in use.
P3351[0...2] BI: Super torque enable This parameter defines the source of the super torque enable.
The setting is effective when P3352 = 2.
Factory default: 0 (never enabled)
P3352[0...2] Super torque startup mode This parameter defines when the super torque function
becomes active.
= 0: Enabled on first run after power-up
= 1: Enabled on every run
= 2: Enabled by digital input (enable source is defined by
P3351; 0 = never enabled, 1 = enabled on every run)

Table of Contents

Other manuals for Siemens SINAMICS V20 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS V20 Series and is the answer not in the manual?

Siemens SINAMICS V20 Series Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS V20 Series
CategoryDC Drives
LanguageEnglish

Related product manuals