Commissioning
5.6 Function commissioning
SINAMICS V20 Inverter
96 Operating Instructions, 07/2012, A5E03728167
5.6.3.11 Running the inverter in sleep mode
Functionality
The motor is turned off if demand falls below threshold, and turned on if demand rises above
threshold.
5HTXLUHGUHVSRQVHRIVLPSOHKLEHUQDWLRQVOHHSPRGH
'HPDQG
IUHTXHQF\
2XWSXW
IUHTXHQF\
+LEHUQDWLRQ +LEHUQDWLRQ
21GHOD\
21GHOD\
2))GHOD\
2))GHOD\
)PLQ
)PLQ
3 3
33
Setting parameters
Parameter Function Setting
P2365[0...2] Hibernation enable / disable This parameter enables or disables the hibernation
functionality.
= 0: Disabled (factory default)
= 1: Enabled
P2366[0...2] Delay before stopping motor [s] With hibernation enabled, this parameter defines the delay
before the inverter goes into sleep mode.
Range: 0 ... 254 (factory default: 5)
P2367[0...2] Delay before starting motor [s] With hibernation enabled, this parameter defines the delay
before the inverter comes out of sleep mode.
Range: 0 ... 254 (factory default: 2)
P1080[0...2] Minimum frequency [Hz] Sets minimum motor frequency at which motor will run
irrespective of frequency setpoint. Value set here is valid both
for clockwise and for anticlockwise rotation.
Range: 0.00 ... 599.00 (factory default: 0.00)

Table of Contents

Other manuals for Siemens SINAMICS V20 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS V20 Series and is the answer not in the manual?

Siemens SINAMICS V20 Series Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS V20 Series
CategoryDC Drives
LanguageEnglish

Related product manuals