5.6.3.11 Running the inverter in sleep mode
Functionality
The motor is turned off if demand falls below threshold, and turned on if demand rises above
threshold.
5HTXLUHGUHVSRQVHRIVLPSOHKLEHUQDWLRQVOHHSPRGH
'HPDQG
IUHTXHQF\
2XWSXW
IUHTXHQF\
+LEHUQDWLRQ +LEHUQDWLRQ
21GHOD\
21GHOD\
2))GHOD\
2))GHOD\
)PLQ
)PLQ
3 3
33
Setting parameters
Parameter Function Setting
P2365[0...2] Hibernation enable / disable This parameter enables or disables the hibernation
functionality.
= 0: Disabled (factory default)
= 1: Enabled
P2366[0...2] Delay before stopping motor [s] With hibernation enabled, this parameter defines the delay
before the inverter goes into sleep mode.
Range: 0 ... 254 (factory default: 5)
P2367[0...2] Delay before starting motor [s] With hibernation enabled, this parameter defines the delay
before the inverter comes out of sleep mode.
Range: 0 ... 254 (factory default: 2)
P1080[0...2] Minimum frequency [Hz] Sets minimum motor frequency at which motor will run
irrespective of frequency setpoint. Value set here is valid both
for clockwise and for anticlockwise rotation.
Range: 0.00 ... 599.00 (factory default: 0.00)