Safety, approvals, EMC
7.2 Test voltage
SITOP PSU100S
56 Operating Instructions, 02.2013, C98130-A7589-A1-3-7629
7.2 Test voltage
*URXQG3(
6HFRQGDU\3ULPDU\,QSXW 2XWSXW


$
%
&
Figure 7-1 Test voltage diagram
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Tests (A) & (B)
Connect the input terminals with one another (L, N)
Connect the output terminals, signaling contact and PE with one another
Test (C)
Connect the output terminals and signaling contact with one another and measure with
respect to PE
Table 7- 1 Test voltage
Test time Prim ↔ sec (A) Prim ↔ PE (B) Sec ↔ PE (C)
60 s 4200 VDC 2200 VDC 700 VDC Type test
60 s 3000 VAC 1500 VAC 500 VAC
1 s 2200 VDC 2200 VDC 500 VDC Production test
1 s 1500 VAC 1500 VAC 350 VAC
1 s 2200 VDC 2200 VDC 500 VDC Field test
1 s 1500 VAC 1500 VAC 350 VAC
Remark:
Tripping current for DC measurement: 0 mA
Tripping current for AC measurement: <100 mA