Users Guide
79
Function configuration:
Connections
Connect the output of the Pass-through Turn Generator to the input and output of the
Circuit Breaker of the recloser. This can be done in one single pole or in the three poles
connected together in series.
Test:
Set a higher output current value than the trip set value in the over current element of the
protection integrated into the recloser, to ensure that it trips. After that, the function
automatically detects the trips and the reclosing times due to the appearance and
disappearance of current in the generator circuit, and the automatic opening and
reclosing process must be continuously carried out by the device being tested.
The device keeps the function running until the maximum test time has elapsed (8 s by
default) or the manual stop condition has been fulfilled (by default this is by pushbutton),
if the relay has completed the number of retries that have been set.
It is recommendable to use the generation current measurement range that adapts better
to the current level that is going to be injected.
Number of
total trips
Time elapsed
from the first
trip to the last.
Time of last
trip
Fault current value
Area where the
opening and closing
times are shown.