88
Delete digital input manner: select a digital input manner that needs to be deleted, and click
Clear data.
8.3.2.6 Country Mode
If the dispatching input must be the national power dispatching instruction, the Reactive
Control Mode is set to Country mode.
Step 1 Click “Power control→Reactive power” to enter the reactive power interface.
Step 2 Set the Reactive Control Mode to Country mode.
Step 3 Select Country, PPC type and Instruction Type respectively from the drop-down lists, enter
Forwarding Modbus ID, and then click Save.
- - End
8.3.2.7 Disable Dispatching
Set the Reactive Control Mode to Disable Dispatching if the Logger1000 is prohibited to
perform reactive dispatching on the inverter.
Step 1 Click “Power control→Reactive power” to enter the reactive power interface.
Step 2 Set the Reactive Control Mode to Disable Dispatching and click Save.
- - End
8.3.3 Emergency Button
In inverters need to be stopped in batch, select the button Emergency Button.
Click “Power control→Emergency button” to enter the corresponding interface.
Parameter
Description
Emergency button
Enable: The emergency button is turned on, and inverters are
stopped in batch.
Note:When the emergency button is recovered, and inverters are
still in standby mode. It is required to boot the inverters manually
via logger or other approaches.
DI port Associated with DI5 channel
8 Grid Dispatching Function User Manual