109
9
Troubleshooting and Maintenance
9.1 Troubleshooting
Once the inverter fails, the fault information is displayed on the App interface. If the inverter
is equipped with an LCD screen, the fault information can be viewed on it.
The fault codes and troubleshooting methods of all PV inverters are detailed in the table be-
low, and only some of the faults may occur to the model you purchased. When a fault occurs,
you can check the fault information according to the fault code on the mobile app.
Fault Code Fault Name Corrective Measures
2, 3, 14, 15
Grid Overvoltage
Generally, the inverter will be reconnected to the
grid after the grid returns to normal. If the fault oc-
curs repeatedly:
1. Measure the actual grid voltage, and contact
the local electric power company for solutions if
the grid voltage is higher than the set value.
2. Check whether the protection parameters are
appropriately set via the App or the LCD. Modify
the overvoltage protection values with the con-
sent of the local electric power operator.
3. Contact Sungrow Customer Service if the pre-
ceding causes are ruled out and the fault persists.
4, 5
Grid Undervoltage
Generally, the inverter will be reconnected to the
grid after the grid returns to normal. If the fault oc-
curs repeatedly:
1. Measure the actual grid voltage, and contact
the local electric power company for solutions if
the grid voltage is lower than the set value.
2. Check whether the protection parameters are
appropriately set via the App or the LCD.
3. Check whether the AC cable is firmly in place.
4. Contact Sungrow Customer Service if the pre-
ceding causes are ruled out and the fault persists.

Table of Contents

Other manuals for Sungrow SG20RT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG20RT and is the answer not in the manual?

Sungrow SG20RT Specifications

General IconGeneral
ModelSG20RT
CategoryInverter
Max. DC Voltage1100 V
Rated AC Power Output20 kW
Max. Efficiency98.6%
Max. DC Input Power30 kW
Max. Input Voltage1100 V
Start Voltage200 V
Number of MPPTs2
Number of DC Inputs per MPPT2
Max. AC Apparent Power22 kVA
Rated Grid Frequency50 Hz / 60 Hz
Max. Output Current32 A
Power Factor at Rated Power>0.99
THDi<3%
DC SwitchYes
Protection ClassIP65
Cooling MethodNatural Convection
Protection DegreeIP65
Protection LevelIP65
MPPT Voltage Range200 V - 1000 V
Operating Temperature Range-25°C to +60°C
Input Voltage Range200 V - 1000 V
MPPT Range200 V - 1000 V
AC Voltage Range310 V - 480 V