35
The external protective grounding terminal must meet at least one of the following
requirements.
The cross-sectional area of the grounding cable is not less than 10 mm
2
for cop-
per wire or 16 mm
2
for aluminum wire. It is recommended that both the external
protective grounding terminal and the AC side grounding terminal be reliably
grounded.
If the cross-sectional area of the grounding cable is less than 10 mm
2
for copper
wire or 16 mm
2
for aluminum wire, ensure that both the external protective
grounding terminal and the AC side grounding terminal are reliably grounded.
The grounding connection can be made by other means if they are in accordance
with the local standards and regulations, and SUNGROW shall not be held liable
for the possible consequences.
5.4.1 External Protective Grounding Requirements
All non-current carrying metal parts and device enclosures in the PV power system should
be grounded, for example, brackets of PV modules and inverter enclosure.
When there is only one inverter in the PV system, connect the external protective grounding
cable to a nearby grounding point.
When there are multiple inverters in the PV system, connect the external protective ground-
ing terminals of all inverters and the grounding points of the PV module brackets to ensure
equipotential connections to ground cables (according to the onsite conditions).
5.4.2 Connection Procedure
External grounding cable and OT/DT terminal are prepared by customers.
step 1 Prepare the cable and OT/DT terminal.
User Manual 5 Electrical Connection

Table of Contents

Other manuals for Sungrow SG20RT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG20RT and is the answer not in the manual?

Sungrow SG20RT Specifications

General IconGeneral
ModelSG20RT
CategoryInverter
Max. DC Voltage1100 V
Rated AC Power Output20 kW
Max. Efficiency98.6%
Max. DC Input Power30 kW
Max. Input Voltage1100 V
Start Voltage200 V
Number of MPPTs2
Number of DC Inputs per MPPT2
Max. AC Apparent Power22 kVA
Rated Grid Frequency50 Hz / 60 Hz
Max. Output Current32 A
Power Factor at Rated Power>0.99
THDi<3%
DC SwitchYes
Protection ClassIP65
Cooling MethodNatural Convection
Protection DegreeIP65
Protection LevelIP65
MPPT Voltage Range200 V - 1000 V
Operating Temperature Range-25°C to +60°C
Input Voltage Range200 V - 1000 V
MPPT Range200 V - 1000 V
AC Voltage Range310 V - 480 V

Related product manuals