10.10.4 Reactive Power Setting for Italy
If the “Countries” selected is “IT” (Italy), several LCD menus and operation methods
are different from other countries.
The differences focus on “Run-param” as shown below.
Italy “Q(P)” Mode
Power factor changes with the output power of the
inverter.
Select Q(P) mode and Press to enter into the
“Run-para-Q(P)” sub-menu.
Press to move the cursor; Press to enter the
editing mode, then the selected parameter will be
shaded.
Press to increase one-step value; Press to
decrease one-step value.
Press ENTER to confirm the setting and exit from the
editing mode.
Tab. 10-8 Italy “Q(P)” Mode Parameters Explanation
Parameter Explanation Default Range Step
PA*
Active power at point A (in %)
20% 20~100% 1%
PB*
Active power at point B (in %)
50% 20~100% 1%
PC*
Active power at point C (in %)
100% 20~100% 1%
Pf max Power factor at point C 0.9 0.9~1 0.01
Uin**
Enter Q(P) regulation mode
when grid voltage is above
Uin
105% 100~110% 1%
Uout**
Exit from the Q(P) regulation
mode when grid voltage is
below Uout
100% 90~100% 1%
*PA < PB≤ PC ** Uin>Uout