10 Operation of LCD Display User Manual
84
10.12 Communication Parameter Setting
Main Screen (Press ENTER)→Menu (Press ×3)→Set-param (Press ENTER)→Enter
password (Press ENTER, Press ×3)→Com-param (Press ENTER)
Press to move cursor and press to
set the appropriate value. Confirm
settings by Pressing ENTER.
Device address range: 1-247.
Baud rate can be set to 9600bps or
19200bps.
Parity can be set to NO, ODD or EVEN.
Stop bit can be set to 1b or 2b.
10.13 Advanced Parameters Setting
The inverter provides a variety of advanced protection features.
Main Screen(Press ENTER)→Menu (Press ×3)→Set-param (Press ENTER)→Enter
password (Press ENTER, Press ×4)→Advanced settings(Press ENTER)
10.13.1 10min Max-V
Main Screen(Press ENTER)→Menu (Press ×3)→Set-param (Press ENTER)→Enter
password (Press ENTER, Press ×4)→Advanced settings(Press ENTER)→10min
Max-V(Press ENTER)
User can only check the parameter in this interface. The default values of the
advanced parameters have been preset as per grid code of corresponding countries.
To set the advanced parameters , please contact Sungrow to acquire advanced
password.