Energier Apollo User Manual
44
Energier Apollo default rated AC voltage is 230V and can be set to 220V or 240V. Also rated
frequency can be set to 50 or 60Hz.
Usually battery charging curve setting is not necessary. If the preset charging parameters are not
suitable for the battery installed with Energier Apollo, following charging parameters can be
changed on the LCD display.
6.5 How to set battery charging curve
6.6 How to set inverter parameters
Note:
1) All of charging parameters should be complied with battery datasheet, otherwise
battery may be damaged.
2) The temperature compensation function is only suitable for lead acid battery. The
compensation coefficients is - 4mV/cell/based on 25. The charging voltage
decreases by 4mV per cell for every 1 degree Celsius rise in temperature.
6.6.1 Rated AC voltage and frequency
General
Advanced
Enter
ESC
Page
down x 3
Page up
Rated voltage
230V
Absorption
57.6 V
Floating
voltage
54.0 V
Temperature
-4.0mv/cell/
compensation voltage
Charge rate
15%
Page down
Page up
Page down
Page up
Page down
Page up
General
Advanced
Enter
ESC
Page down
Page up
Rated voltage
230V
50
Rated frequency
Hz

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the TBB Energier Apollo CH3.0S and is the answer not in the manual?

TBB Energier Apollo CH3.0S Specifications

General IconGeneral
BrandTBB
ModelEnergier Apollo CH3.0S
CategoryInverter
LanguageEnglish

Related product manuals