Note 1: Criteria for the difference between suction and discharge temperatures
(1) Cooling operation
After operating for a minimum of 30 minutes in “COOL” mode, if the T dry bulb temperature difference
between suction and discharge air of the indoor unit is 8°C or more, it is normal.
(2) Heating operation
After operating for a minimum of 30 minutes in “HEAT” mode, if the T dry bulb temperature difference
between suction and discharge air of the indoor unit is 15°C or more, it is normal.
* If demand from the indoor unit on the outdoor unit is low because the difference between the temperature
set by the remote controller and the temperature of the room is small, then the T temperature difference is
small.
* Consider that T temperature difference may diminish in cases of a system in which the connected indoor
unit capacity exceeds the outdoor unit capacity, the pipe length is long, or a large difference exists among
outdoor units.
Note 2: Criteria for operating power current
The table below shows the maximum current for each outdoor unit. Under standard conditions, operating
current is about 80% of the value shown in the table below.
Model
Current value
Model
Current value
MMY-MUP
(A)
MMY-MUP
(A)
0801*
15.4
14A1*
27.0
1001*
20.5
1801*
34
1201*
24.5
2001*
36
1401*
27.5
2201*
51
2401*
54
Note 3: Criteria for cycle status
(1) These data are based on operating a 4-way Air Discharge Cassette type air conditioner of 100%
connection with standard piping length.
Data may vary depending on temperature conditions, installed pipe length, and room shape combinations,
or indoor unit connection capacity.
For pressure criteria in different temperature conditions, refer to (2).
* This compressor is driven with a 6-pole motor. The value of the compressor frequency (rps) measured with a
clamp meter at the compressor lead line is three times the rotation count (rps) of the compressor
.
* Each compressor may have a different frequency as a measure against resonance.
* The temperature of the indoor heat exchanger (TC) indicates TCJ sensor temperature when cooling, and
TC2 sensor temperature when heating, respectively.
Operating
Mode
Pressure
(MPa)
Temperature
㧔
ºC
㧕
Indoor
18 ~ 32
15 ~ 32
PS
0.5 ~ 0.9
0.5 ~ 0.7
Pd
2.0 ~ 3.3
2.5 ~ 3.3
Cooling
Heating
Outdoor
25 ~ 35
5 ~ 35
(2) Criteria for operating pressure
* Criteria after 14 minutes or more has passed since operating started
1601*
30.5
Pipe Surface Temperature Compressor Rotation Air Temperature
Outdoor
Pressure
(ºC) (rps) (DB/WB)(ºC)
Unit
Operating
(MPa)
Indoor
Indoor Heat Outdoor Heat Liquid
MMY-MUP
Mode
Discharge Suction
Exchanger Exchanger Temperature
Compressor 1 Compressor 2
Fan
Outdoor Indoor
Pd
Ps
TD1
TS1
TC2
TE1 TL3
Cmp. 1
Cmp. 2 TO
TA
Cooling
3.0
1.0
79
21
15
39 26
50
High
35
27
0801*
Heating
2.4
0.7
67
2
25
1 21
57
High
7
20
Cooling
3.1
1.0
82
21
15
40 26
56
High
35
27
1001*
Heating
2.8
0.7
79
2
23
0 17
63
High
7
20
Cooling
3.4
1.1
86
21
15
40 29
65
High
35
27
1201*
Heating
2.5
0.7
75
1
25
0 16
75
High
7
20
Cooling
3.7
1.1
91
20
16
41 33
77
High
35
28
1401*
Heating
2.4
0.7
73
1
26
-1
22
83
High
7
20
Cooling
3.1
1.0
81
19
15
41 33
77
High
27
14A1*
35
Heating
2.5
0.7
73
1
26
-1
22
83
High
7
20
1601*
Cooling
3.2
1.0
85
19
15 43
28
65
High
35
27
Heating
2.5
0.6
71
-1
27 1
17
68
High
7 20
1801*
Cooling
3.4
1.0
90
19
14 42
28
70
High
35 27
Heating
2.5
0.6
72
-2
27 2
22
77
High
7 20
2001*
Cooling
3.3
0.9
92
20
14 43
31
77
High
35 27
Heating
2.5
0.6
79
0
25 0
1
82
High
7
20
2201*
Cooling
3.5
1.0
94
27
15 42
29
71 70
High
35
27
Heating
2.7
0.6
82
-1
25 0
-4
79 77
High
7
20
2401*
Cooling
3.7
1.0
98
21
15 43
30
78 77
High
35
27
Heating
2.6
0.6
81
-1
24 0
20
79 77
High
7
20
―
―
―
―
―
―
―
―
―
―
―
―
―
―