EasyManuals Logo
Home>Toshiba>Inverter>TOSVERT VF-S15 series

Toshiba TOSVERT VF-S15 series Manual

Toshiba TOSVERT VF-S15 series
51 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #43 background imageLoading...
Page #43 background image
E6581911
- 42 -
1. NMT Boot-up (Drive power on)
INV - PC
COB-ID
RTR
DLC
Data0
Data1
Data2
Data3
Data4
Data5
Data6
Data7
0x701
0
1
0
---
---
---
---
---
---
---
*1: If VF-AS3 is used, EMCY (Drive power on) is sent.
INV - PC
COB-ID
RTR
DLC
Data0
Data1
Data2
Data3
Data4
Data5
Data6
Data7
0x81
0
8
0
0
0
0
0
0
0
0
2. NMT Module Control (Change Operational state)
INV - PC
COB-ID
RTR
DLC
Data0
Data1
Data2
Data3
Data4
Data5
Data6
Data7
0x000
0
2
1
1
---
---
---
---
---
---
TxPDO1 (Send the response of the drive status and the output frequency)
INV - PC
COB-ID
RTR
DLC
Data0
Data1
Data2
Data3
Data4
Data5
Data6
Data7
0x181
0
4
Status word
vl_velocity
_actual_value
---
---
---
---
0x50
0x02
0
0
3.RxPDO1 (Change to Ready to switch on state)
INV - PC
COB-ID
RTR
DLC
Data0
Data1
Data2
Data3
Data4
Data5
Data6
Data7
0x201
0
4
Control word
vl_target_velocity
---
---
---
---
0x06
0x00
0x00
0x00
TxPDO1 (Send the response of the drive status and the output frequency)
INV - PC
COB-ID
RTR
DLC
Data0
Data1
Data2
Data3
Data4
Data5
Data6
Data7
0x181
0
4
Status word
vl_velocity
---
---
---
---
0x31
0x02
0x00
0x00
4. RxPDO1 (Change Switch on state)
INV - PC
COB-ID
RTR
DLC
Data0
Data1
Data2
Data3
Data4
Data5
Data6
Data7
0x201
0
4
Control word
vl_target_velocity
---
---
---
---
0x07
0x00
0x00
0x00
TxPDO1 (Send the response of the drive status and the output frequency)
INV - PC
COB-ID
RTR
DLC
Data0
Data1
Data2
Data3
Data4
Data5
Data6
Data7
0x181
0
4
Status word
vl_velocity
---
---
---
---
0x33
0x02
0x00
0x00
5. RxPDO1 (Change Operation enable state)
INV - PC
COB-ID
RTR
DLC
Data0
Data1
Data2
Data3
Data4
Data5
Data6
Data7
0x201
0
4
Control word
vl_target_velocity
---
---
---
---
0x0f
0x00
0x00
0x00
TxPDO1 (Send the response of the drive status and the output frequency)
INV - PC
COB-ID
RTR
DLC
Data0
Data1
Data2
Data3
Data4
Data5
Data6
Data7
0x181
0
4
Status word
vl_velocity
---
---
---
---
0x37
0x02
0x00
0x00
6. RxPDO1 (Set the speed to 1500min
-1
(0x05dc))
INV - PC
COB-ID
RTR
DLC
Data0
Data1
Data2
Data3
Data4
Data5
Data6
Data7
0x201
0
4
Control word
vl_target_velocity
---
---
---
---
0x0f
0x00
0xdc
0x05
TxPDO1 (Send the response of the drive status and the output frequency)
INV - PC
COB-ID
RTR
DLC
Data0
Data1
Data2
Data3
Data4
Data5
Data6
Data7
0x181
0
4
Status word
vl_velocity
---
---
---
---
0x37
0x06
0xdc
0x05

Table of Contents

Other manuals for Toshiba TOSVERT VF-S15 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S15 series and is the answer not in the manual?

Toshiba TOSVERT VF-S15 series Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-S15 series
CategoryInverter
LanguageEnglish

Related product manuals