EasyManuals Logo
Home>Toshiba>Inverter>TOSVERT VF-S15 series

Toshiba TOSVERT VF-S15 series Manual

Toshiba TOSVERT VF-S15 series
51 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #22 background imageLoading...
Page #22 background image
E6581911
- 21 -
5.1.3. PDO object
PDO1 to PDO3 and PDO21.
PDO set
RPDO
TPDO
Note
PDO1
Controlword
Statusword
COB-ID is variable mapping.
TPDO1 : 0x00000180+Node-ID
RPDO2 : 0x00000200+Node-ID
vl_target_velocity
vl_velocity_actual_value
variable mapping
variable mapping
variable mapping
variable mapping
PDO2
variable mapping
variable mapping
COB-ID is variable mapping.
TPDO2 : 0x00000280+Node-ID
RPDO2 : 0x00000300+Node-ID
variable mapping
variable mapping
variable mapping
variable mapping
variable mapping
variable mapping
PDO3
variable mapping
variable mapping
COB-ID is variable mapping.
TPDO3 : 0x00000380+Node-ID
RPDO3 : 0x00000400+Node-ID
variable mapping
variable mapping
variable mapping
variable mapping
variable mapping
variable mapping
PDO21
variable mapping
variable mapping
COB-ID is variable mapping.
TPDO21 : 0x00000480+Node-ID
RPDO21 : 0x00000500+Node-ID
variable mapping
variable mapping
variable mapping
variable mapping
variable mapping
variable mapping
5.1.4. RPDO object
Index
(Hex)
Sub
index
Access
Type
Default value
Description
1400
00
R
u8
0x02
Receive PDO1: Number of objects
01
R/W
u32
0x00000200
+ Node-ID
Receive PDO1: COB-ID entry
The default value is 0x00000200 (parameter data c711)
+Node-ID. If set other than 0x00000200 except bit31, new set
data is used for COB-ID (=new data).
Bit31 is an enable/disable flag of RPDO1 data set.
02
R
u8
0x0FF
Receive PDO1: Transmission type
“asynchronous” (254 or 255), “synchronous” (0 - 240).
1401
00
R
u8
0x02
Receive PDO2: Number of objects
01
R/W
u32
0x80000300
+ Node-ID
Receive PDO2 COB-ID entry
The default value is 0x80000300 (parameter data c721)
+Node-ID. If set other than 0x80000300 except bit31, new set
data is used for COB-ID (=new data).
Bit31 is an enable/disable flag of RPDO2 data set.
02
R/W
u8
0x0FF
Receive PDO2: Transmission type
“asynchronous” (254 or 255), “synchronous” (0 -240).
1402
00
R
u8
0x02
Receive PDO3: Number of objects
01
R/W
u32
0x80000400+
Node-ID
Receive PDO3 COB-ID entry
The default value is 0x00000400 (parameter data c731)
+Node-ID. If set other than 0x80000400 except bit31, new set
data is used for COB-ID (=new data).
Bit31 is an enable/disable flag of RPDO3 data set.
02
R/W
u8
0x0FF
Receive PDO3: Transmission type
“asynchronous” (254 or 255), “cyclic synchronous” (0 -240).
1414
00
R
u8
0x02
Receive PDO21: Number of objects
01
R/W
u32
0x80000500
+ Node-ID
Receive PDO21 COB-ID entry
The default value is 0x80000500 (parameter data c741)
+Node-ID. If set other than 0x80000500 except bit31, new set
data is used for COB-ID (=new data).
Bit31 is an enable/disable flag of RPDO21 data set.
02
R/W
u8
0x0FF
Receive PDO21: Transmission type
“asynchronous” (254 or 255), “synchronous” (0 -240).

Table of Contents

Other manuals for Toshiba TOSVERT VF-S15 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S15 series and is the answer not in the manual?

Toshiba TOSVERT VF-S15 series Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-S15 series
CategoryInverter
LanguageEnglish

Related product manuals