E6581911
- 16 -
4.2. Communication parameters
Set up the parameters before the communication is started. The parameters with hatching are
communication profile. Normally, these parameters are downloaded by SDO sever object. Refer to
5.1Communication Profile (DS 301)”.
Title
Parameter function
Default
Value
Note
f856
Number of motor poles for
communication
2
2: 4 pole
f898
Drive reset mode selection
0
0: Clear trip by request from
communication option. Reset by request
except from communication option.
1: All reset
2: Trip clear
3-5: - [VF-AS3]
f899
Communication function reset
0
0: -
1: Reset (after execution: 0)
Title
Parameter function
Default
Value
Note
c100
Communication time out
0.0
0.0 to 100.0 sec
c101
Drive operation at the
communications loss action
(Guard Time, Heartbeat)
4
0: Stop and Communication release (follows
cmod and fmod setting)
(Do not set at Software is Ver. 1.00.)
1: None
2: Deceleration stop
3: Coast stop
4: Emergency stop
5: Preset speed operation command
(Operating at the preset speed operation
frequency set with c102)
c102
Preset speed operation
selection
0
0: None
1 to 15:Preset speed
c103
Communication time-out
condition selection
1
0: Disconnection detection
1: When communication mode enable (Both
cmod and fmod are set CANopen or
COM option)
2:1+Driving operation
c701
Node ID
0
0: Disable CANopen
1 ~ 127 : Node ID
c702
Baud rate
0: 20k 4: 500k
1: 50k 5: 800k
2: 125k 6: 1M
3: 250k
2
(125kbps)
CAN communication baud rate
c703
SYNC message COB-ID
0x0080
0x1005 Set Lower word
c704
Guard Time:
0
0x100C 1ms unit
c705
Life Time Factor:
0
0x100D from 0 to 255
c706
Node-ID of Heartbeat Producer
0x0000
0x1016
Bits 16-23 = Node-ID of Heartbeat Producer
Bits 24-31 = Reserved (00)
c707
Max. duration of Consumer
Heartbeat
0x0000
0x1016
Bits 00-15 = Max. duration of Consumer
Heartbeat (unit = 1 ms)
Note: A single Heartbeat Producer can be
configured here. By default, no producers are
monitored (value = 0).
c708
Producer Heartbeat Time:
0
0x1017 1ms unit

Table of Contents

Other manuals for Toshiba TOSVERT VF-S15 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S15 series and is the answer not in the manual?

Toshiba TOSVERT VF-S15 series Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-S15 series
CategoryInverter
LanguageEnglish

Related product manuals