80 BAS-SVX45F-GB
Appendix A: Configuring Tracer UC600 for BACnet/IP
Figure 45. Configuring IP information
Configuring BACnet Information
1. Navigate to the BACnet Settings frame.
2. In the Device ID section, use the current device ID or select the Use Software Device ID check
box and enter the device ID. (For more information about device IDs, see
“Device ID Assignment
for Trane BACnet/IP Devices,” p. 76.
3. In the Protocol section, select the Enable BACnet/IP Communications radio button, and then
assign a UDP Port number. All devices on a BACnet/IP network must have the same UDP port
number.
4. Determine whether the Tracer UC600 must be a BBMD. If the device is BBMD, set up a BDT (See
“Setting Up a BDT,” p. 81.
5. After all edits are complete, click Send to Device.
6. To return to the Startup Task Panel, disconnect from Tracer TU and then reconnect.