BAS-SVX45F-GB 9
Overview
Hardware Terminations
Tracer UC600 supports the following hardware terminations:
• Temperature sensors (resistive and thermistor)
• Linear inputs 0–20 mA, such as humidity sensors
• Linear inputs 0–10 VDC, such as indoor air-quality sensors
• Linear outputs 0-20 mA, such as variable frequency drives
• Linear outputs 0–10 VDC, such as accuators for dampers and valves
• Pulse outputs, such as electric heat or humidifier control
• Binary outputs, such as fan start/stop
• One 3-wire pressure transducer input
Table 2. UC600 device connections
Input/Output type Quantity Types Range Notes
Universal input
8
Thermistor
10kΩ – Type II, 10kΩ –Type III,
2252Ω – Type II, 20kΩ – Type IV,
100kΩ
Resistive (Setpoint) 100Ω – 1MΩ
RTD
Balco™ (Ni-Fe), 1kΩ; 375 (Pt),
385 (Pt), 1kΩ
Current 0–20 mA (linear)
Voltage 0–20 VDC (linear)
Binary Dry contact
Pulse Width Accumulator Minimum 20 ms, opened or closed
Universal Input/Analog
Output
Configure using any combination of analog or binary inputs/analog outputs
6
Thermistor
10kΩ – Type II, 10kΩ –Type III,
2252Ω – Type II, 20kΩ – Type IV,
100kΩ
The UC600 provides 600 mA of DC power for 0–
20 mA inputs and/or outputs, and to power
expansion modules. See the power budget
table “Power Budget Check in an Un-powered
State,” p. 21.
Inputs
Resistive (setpoint) 100Ω –1MΩ
RTD
Balco™ (Ni-Fe), 1kΩ; 375 (Pt),
385 (Pt), 1kΩ
Current 0–20 mA (linear)
Voltage 0–20 VDC (linear)
Binary Dry contact
Pulse Width Accumulator Minimum 20 ms, opened or closed
Outputs
Current 0–20 mA @16 V
Voltage 0–10 VDC @20 mA
Pulse
12.5ms to 1 second (12.5ms
resolution), 1 second to 60 seconds
(0.5 second resolution)
Binary output 4 Relay (form A) wet 24 VAC, 0.5A maximum Ranges are given per contact.
Pressure input 1 3-wire 0–5 inwc.
Pressure input supplied with 5 VDC. Designed for
Kavlico™ pressure transducers.
Point total 19