Technical data
General
IP IP30 (IP: degree of inaccessibility to active parts of the product
and degree of water)
Max. ambient RH (relative humidity) 85% at 20 °C
Thermostat
CE marking
Low voltage tests EN 60730-1* and EN 60730-2-9***
EMC (electromagnetic compatibility requirements) tests EN 60730-1 and EN 301-489-3
ERM (electromagnetic compatibility and radio spectrum matters) tests EN 300 220-3
Power supply Two 1.5 V AAA alkaline batteries
Voltage 2.2 V to 3.6 V
Operating temperature 0 °C to +45 °C
Storage temperature -10 °C to +65 °C
Radio frequency 868.3 MHz
Transmitter duty cycle <1%
Connection terminals (thermostats only) 0.5 mm² to 2.5 mm²
Antenna
Power supply 5 V DC ±10 % from controller
Maximum power consumption 1 W
Radio frequency 868.3 MHz
Transmitter duty cycle 1%
Receiver class 2
Controller
CE marking
Low voltage tests EN 60730-1* and EN 60730-2-1**
EMC (electromagnetic compatibility requirements) tests EN 60730-1 and EN 301-489-3*
ERM (electromagnetic compatibility and radio spectrum matters) tests EN 300 220-3*
Power supply 230 V AC +10/-15%, 50 Hz
Operating temperature 0 °C to +50 °C
Storage temperature -20 °C to +70 °C
Maximum consumption 75 W
Pump 1 output 230 V AC +10/-15%, 250 V AC 5 A maximum (L, N, PE)
Heating output 230 V AC +10/-15%, 250 V AC 5 A maximum (L, N, PE)
Cooling/pump 2 output 230 V AC +10/-15%, 250 V AC 5 A maximum (L, N, PE)
3-point control 2 TRIACS => 75 W max
Valve output 230 V AC ±10%,
Power connection 1 m cable with europlug
Connection terminals Up to 4.0 mm² solid, or 2.5 mm² fl exible with ferrules
*) EN 60730-1 Automatic electrical controls for household and similar use
-- Part 1: General requirements
**) EN 60730-2-1 Automatic electrical controls for household and similar use
-- Part 2-1: Particular requirements for electrical controls for electrical
household appliances
***) EN 60730-2-9 Automatic electrical controls for household and similar use
-- Part 2-9: Particular requirements for temperature sensing controls
0682
Usable in all Europe
Declaration of conformity:
We hereby declare under our own responsibility that products dealt
with by these instructions satisfy all essential demands linked to the
R&TTE 1999/5/CE Directive dated March 1999.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Uponor Smatrix Move PLUS and is the answer not in the manual?

Uponor Smatrix Move PLUS Specifications

General IconGeneral
BrandUponor
ModelSmatrix Move PLUS
CategoryThermostat
LanguageEnglish

Related product manuals