EasyManuals Logo
Home>Xinje>Inverter>VB5N Series

Xinje VB5N Series User Manual

Xinje VB5N Series
105 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #58 background imageLoading...
Page #58 background image
VB5N series inverter
50
P0.15
Linear time of S curve
Range: 10.0%~80.0% (Acc/Dec time), P0.14P0.15<90%
60.0%
P0.14 and P0.15 are only valid when Acc/Dcc mode is S curve Acc/Eec mode (P0.13 1) and P0.14+P0.15 < 90%.
Low speed time of S curve is shown in Fig.4-5 , the output frequency slope increases from 0.
Linear part time of S curve is shown in Fig.4-5 , the output frequency slope is constant.
High speed time of S curve is shown in Fig.4-5 , the output frequency slope decreases to 0.
High speed time100%P0.14P0.15.
Note: S curve Acc/Dec mode is suitable for the start/stop of elevator, conveying belt, conveying load and so on.
P0.16
Acc/Dec time unit
Range: 0, 1
0
This function defines Acc/Dec time unit
0: second
1: minute
Note: (1) This function is valid for all the Acc/Dec mode except jog running.
(2) Second unit is recommended.
P0.17
Acc time 1
Range: 0.1~6000.0
10.0
P0.18
Dec time 1
Range: 0.1~6000.0
10.0
Acc time is the time accelerating from 0 Hz to highest frequency, see t
1
in Fig.4-6; Dec time is the time decelerating from
highest frequency to 0 Hz, see t
2
in Fig.4-6.
Fig.4-6 Acc/Dec time
Note: (1) This series inverter defines seven kinds of Acc/Dec time. Here only defines Acc/Dec time 1, Acc/Dec time 2~7
are defined in P3.14~P3.25.
(2) Define the Acc/Dcc time unit in P0.16 (minute, second, default is second).
P0.19
Highest frequency
Range: lowest frequency~max output frequency
50.00Hz
P0.20
Lowest frequency
Range: 0.00Hz~highest frequency
0.20HZ
P0.21
Lowest frequency running mode
Range:
0: run with lowest frequency
1: stop
0
P0.19 and P0.20 define the upper and lower frequency, see Fig.4-2 FH(highest frequency) and FL(lowest frequency).
If the actual setting frequency is lower than lowest frequency, inverter will decelerate the output frequency. When it reach
the lowest frequency, if the lowest frequency running mode is 0, inverter will run with lowest frequency. If the lowest
frequency running mode is 1, inverter will decrease the output frequency to 0.
P0.22
V/F curve setting
Range: 0~4
0
P0.23
V/F frequency value F1
Range: 0.00~P0.25
0.00Hz
P0.24
V/F voltage valueV1
Range: 0~P0.26
0.0%
P0.25
V/F frequency value F2
Range: P0.23~P0.27
0.00Hz
t1
t2
Frequency
Upper limit
frequency
time

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xinje VB5N Series and is the answer not in the manual?

Xinje VB5N Series Specifications

General IconGeneral
BrandXinje
ModelVB5N Series
CategoryInverter
LanguageEnglish

Related product manuals