VB5N series inverter
50
Range: 10.0%~80.0% (Acc/Dec time), P0.14+P0.15<90%
P0.14 and P0.15 are only valid when Acc/Dcc mode is S curve Acc/Eec mode (P0.13 =1) and P0.14+P0.15 < 90%.
Low speed time of S curve is shown in Fig.4-5 ③, the output frequency slope increases from 0.
Linear part time of S curve is shown in Fig.4-5 ②, the output frequency slope is constant.
High speed time of S curve is shown in Fig.4-5 ①, the output frequency slope decreases to 0.
High speed time=100%-P0.14-P0.15.
Note: S curve Acc/Dec mode is suitable for the start/stop of elevator, conveying belt, conveying load and so on.
This function defines Acc/Dec time unit
0: second
1: minute
Note: (1) This function is valid for all the Acc/Dec mode except jog running.
(2) Second unit is recommended.
Acc time is the time accelerating from 0 Hz to highest frequency, see t
1
in Fig.4-6; Dec time is the time decelerating from
highest frequency to 0 Hz, see t
2
in Fig.4-6.
Fig.4-6 Acc/Dec time
Note: (1) This series inverter defines seven kinds of Acc/Dec time. Here only defines Acc/Dec time 1, Acc/Dec time 2~7
are defined in P3.14~P3.25.
(2) Define the Acc/Dcc time unit in P0.16 (minute, second, default is second).
Range: lowest frequency~max output frequency
Range: 0.00Hz~highest frequency
Lowest frequency running mode
0: run with lowest frequency
1: stop
P0.19 and P0.20 define the upper and lower frequency, see Fig.4-2 FH(highest frequency) and FL(lowest frequency).
If the actual setting frequency is lower than lowest frequency, inverter will decelerate the output frequency. When it reach
the lowest frequency, if the lowest frequency running mode is 0, inverter will run with lowest frequency. If the lowest
frequency running mode is 1, inverter will decrease the output frequency to 0.