10 Drive Start-Up Procedure
62 YASKAWA TOEPC7106171FD FP605 DRIVE INSTALLATION & PRIMARY OPERATION
The tightening torque for the terminal screws is shown on the reverse side or the lower front side of the front cover.
Figure 10.2 Tightening Torque Display Location (Reverse Side of Front Cover)
Figure 10.3 Tightening Torque Display Location (Lower Front Side of Front Cover)
Control Circuit Wire Gauges and Tightening Torques
Use the tables in this section to select the correct wires. Use shielded wire to wire the control circuit terminal block.
Use crimp ferrules on the wire ends to make the wiring procedure easier and more reliable.
Table 10.6 Control Circuit Wire Gauges and Tightening Torques
Terminal
Block
Terminal Screw Size
Tightening Torque
Nm (lbfin)
Bare Wire Crimp Ferrule
Recommended
Gauge
mm
2
(AWG)
Applicable Gauge
mm
2
(AWG)
Recommended
Gauge
mm
2
(AWG)
Applicable Gauge
mm
2
(AWG)
TB1 +V, AC, A1, A2, A3
M3
0.5 - 0.6
(4.4 - 5.3)
0.75
(18)
Stranded wire:
0.25 - 1.5
(24 - 16)
Solid wire:
0.25 - 1.5
(24 - 16)
0.75
(18)
0.25 - 1.5
(24 - 16)
TB3 FM, AM, AC, S1 - S8
TB4 SN, SC, SP, +P
TB5 SN, HC, H1, H2
TB6 AC, D+, D-, PS, RP
TB7
MA, MB, MC, MD, ME, MF, M1
- M4
TB2 FE
1.0 - 1.2
(8.85 - 10.62)
0.75
(18)
Stranded wire:
0.12 - 0.75
(26 - 18)
Solid wire:
0.2 - 1.5
(26 - 16)
0.75
(18)
0.25 - 1.5
(24 - 16)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA FP65U T Series and is the answer not in the manual?

YASKAWA FP65U T Series Specifications

General IconGeneral
BrandYASKAWA
ModelFP65U T Series
CategoryDC Drives
LanguageEnglish

Related product manuals