13 European Standards
90 YASKAWA TOEPC7106171FD FP605 DRIVE INSTALLATION & PRIMARY OPERATION
Figure 13.2 Wiring Diagram for CE Low Voltage Directive Compliance
*1 For circuit protection, the main circuit is separated from the surface case that can touch the main circuit.
*2 To comply with LVD standard requirement, set L8-05 = 1 [Input Phase Loss Protection Sel = Enabled] to protect the drive from the high
current caused by Input Phase Loss condition.