5. System Functions After Upgrade
5-21
TI 33K01B10-50E
5.3 Application Capacity of Upgraded FCS
When upgrading CENTUM V or CENTUM-XL to CENTUM VP, use a FFCS-V. The table shows
the application capacities of the CENTUM V, CENTUM-XL and CENTUM VP systems.
Table Comparison of Application Capacities
CENTUM V CENTUM-XL CENTUM VP
Function
CFCS2
/CFCD2
CFSS
/CFSD
Function
EFCS
/D-S1
EFCS
/D-H2
Function
General type Batch type
LFS1700
LFS1750
(10 nodes)
LFS1750
(14 nodes)
LFS1700
LFS1750
(10 nodes)
LFS1750
(14 nodes)
Internal
instrument
(DDC calc.)
255 255
Internal
instrument
(DDC calc.)
255 255
Regulatory
control,
calculation
500 1200 1800 400 1000 1500
– – – – – –
Batch data
100 400 600 50 100 150
Arithmetic
expression
255 255
Arithmetic
expression
255 255
General-
purpose
calculation
400 500 750 120 250 350
Sequence
table
40
(99)
200
(255)
Sequence
table
200 200
Sequence
table (S)
Sequence
table (M)
Sequence
table (L)
200
100
100
400
200
200
700
400
300
100
50
50
200
100
100
400
150
150
Timer/
counter/
code I/O
200
99
512
200
Timer/
counter/
code I/O
511 511
Sequence
auxiliary -1
500 700 1100 500 700 1100
Relational
expression
Valve
monitor
99
128
200
128
Relational
expression
Valve
monitor
255
255
255
255
Sequence
auxiliary -2
100 200 300 50 100 150
– – –
Switch
instrument
255 511
Switch
instrument
500 1000 1500 500 1000 1500
– – –
Batch
status
indicator
32 32
Faceplate
120 200 300 50 100 150
– – – – – –
SFC block
40 100 300 100 200 300
Sequence
message
255 255
Sequence
message
255 255
Printout
message
2000 2000 2000 2000 2000 2000
– – –
Message
with data
attached
100 100 – – – – – – –
Message
request
100 100
Message
request
100 100
Message
request
200 200 200 200 200 200
Operator
guide
message
100 100
Operator
guide
message
100 100
Operator
guide
message
1000 1000 1000 1000 1000 1000
– – –
Request
for voice
output
100 100 – – – – – – –
FORTRAN
program
initiation
100 100 – – –
Supervisory
computer
message
for PICOT
9999 9999 9999 9999 9999 9999
High-order
interrupt
request
100 100
High-order
interrupt
request
510 510
Supervisory
computer
event
message
9999 9999 9999 9999 9999 9999
Annunciator
255 255
Annunciator
255 255
Annunciator
2000 2000 2000 2000 2000 2000
Common
switch
512 512
Common
switch
2048 2048
Common
switch
9000 9000 9000 9000 9000 9000
Contact
input
512 512
Contact
input
768 768
Contact
input
1920 4096 4096 1920 4096 4096
Contact
output
Contact
output
Contact
output
- - -
Instrument/
loop
drawing
24 24
Block/1
drawing
100 100 100 100 100 100
- - -
Loop
drawing
200 200
Drawing
200 200(300/400/500) 200 200(300/400/500)
Mar. 27, 2015-00