18 IM 04L41B01-02E
Operation Example in the Setting Mode: Changing the Input Range
Set the input range of channel 2 to thermocouple type T and 0.0 to 400.0°C.
Type T
thermocouple
Channel 2
DX
1
. Display the operation mode screen.
2
. Press MENU once to display the setting menu.
3
. Press the down arrow key once to select Meas channel.
4
. Press the right arrow key once.
Select the Range, Alarm
5
. Press DISP/ENTER once.
Select First-CH
6
. Press the 2 soft key once. The Last-CH is also set to 2.
7
. Press the down arrow key once to move the cursor to Mode.
Basic Operation