Setup Items in Basic Setting Mode and Their Default Values
Alarm
Setup Item Selectable Range or Selections Default Value Setting
Basic settings
Reflash On/Off Off
Rate of change > Decrease 1 to 32 1
Rate of change > Increase 1 to 32 1
Indicator Hold/Nonhold Nonhold
Switch, Relay
Internal Switch > AND None/S01/S01-S02/.../S01-S29/S01-S30 None
Relay > AND None/I01/I01-I02/.../I01-I06
(Depends on the option.)
None
Relay > Action Energize/De_energ Energize
Relay > Hold Hold/Nonehold Nonhold
Hysteresis
Meas CH > High/Low 0.0 to 5.0 0.5
Meas CH > Delta High/Low 0.0 to 5.0 0.0
Math CH > High/Low 0.0 to 5.0 0.0
A/D, Memory
Setup Item Selectable Range or Selections Default Value Setting
Scan interval > Scan mode Normal/Fast Normal
Normal > Scan interval 125ms/250ms
(DX1002, DX1002N, DX1004, DX1004N)
125ms
1s/2s/5s
(DX1006, DX1006N, DX1012, DX1012N)
1s
Normal > A/D integrate Auto/50Hz/60Hz/100ms Auto
Fast > Scan interval 25ms (DX1002, DX1002N, DX1004, DX1004N) 25ms
125ms (DX1006, DX1006N, DX1012, DX1012N) 125ms
Fast > A/D integrate 600Hz 600Hz
Memory > Data kind Display/E+D/Event Display
Burnout, RJC
Setup Item Selectable Range or Selections Default Value Setting
First-CH, Last-CH 1/2/3/.../11/12 (Depends on the model.) 1
Burnout set > Mode Off/Up/Down Off
RJC > Mode Internal/External Internal
RJC > Volt –20000 to 20000µV0
Environment > Operating environment
Setup Item Selectable Range or Selections Default Value Setting
Tag/Channel Tag/Channel Tag
Language English/Japanese English
Remote Controller ID Off/0/1/.../30/31 Off
Temperature C/F C
Environment > View, Message, Input, Alarm
Setup Item Selectable Range or Selections Default Value Setting
View > Trend type T-Y T-Y
View > Partial On/Off Off
View > Trend rate switching On/Off Off
Message > Write group Common/Separate Common
Message > Power-fail message On/Off Off
Message > Change message On/Off Off
Input > Value on over-range Free/Over Over
Alarm > No logging On/Off Off
Setup Items and Default Values