EasyManuals Logo

York YCAV0187 User Manual

York YCAV0187
310 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #175 background imageLoading...
Page #175 background image
175
JOHNSON CONTROLS
FORM 201.21-NM1 (1223)
ACCELERATION/DECELERATION RATE WHEN
STARTING/STOPPING COMPRESSORS
VSD ACCELERATION AND
DECELERATION RATES
The acceleration rate changes with frequency and fol-
lows the guidelines below:
· Between 0 and 50 Hz, the acceleration is 10 Hz/
sec.
· Between 50 and 200 Hz, the acceleration is 30.4
Hz/sec. Even though the accel rate of 30.4 Hz/sec
is possible up to 200 Hz, the frequency (speed) is
limited by the minimum start frequency and the
add a compressor frequency calculation performed
by the micro when bringing on an additional
compressor.
When decelerating, the deceleration rate changes with
frequency and follows the guidelines below:
· Between 200 and 100 Hz, the deceleration time is
30.4 Hz/sec.
· Between 100 and 0 Hz, the deceleration time is 10
Hz/sec.
When a compressor stops, back-spin of the compressor
will often occur as the pressure dierential between
discharge and suction equalizes. This should not be a
cause of concern.
7

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York YCAV0187 and is the answer not in the manual?

York YCAV0187 Specifications

General IconGeneral
BrandYork
ModelYCAV0187
CategoryChiller
LanguageEnglish

Related product manuals