299
JOHNSON CONTROLS
FORM 201.21-NM1 (1223)
OUTSIDE AIR TEMPERATURE SENSOR INPUT VOLTAGE
TEMP. (ºF) VOLTAGE TEMP. (ºF) VOLTAGE TEMP. (ºF) VOLTAGE
0.24 0.68 49.8 2.00 93.3 3.31
1.79 0.71 50.7 2.03 94.4 3.34
3.30 0.74 51.6 2.06 65.6 3.37
4.76 0.77 52.5 2.09 96.8 3.40
6.19 0.80 53.4 2.11 98.0 3.43
7.58 0.83 54.3 2.14 99.2 3.46
8.94 0.85 55.3 2.17 100.4 3.49
10.3 0.88 56.2 2.20 101.6 3.52
11.6 0.91 57.1 2.23 102.9 3.55
12.8 0.94 58.0 2.26 104.2 3.57
14.1 0.97 58.9 2.29 105.5 3.60
15.3 1.00 59.8 2.32 106.8 3.63
16.5 1.03 60.7 2.35 108.1 3.66
17.7 1.06 61.6 2.38 109.5 3.69
18.9 1.09 62.6 2.41 110.9 3.72
20.0 1.12 63.5 2.44 112.3 3.75
21.2 1.15 64.4 2.47 113.8 3.78
22.3 1.18 65.3 2.50 115.2 3.81
23.4 1.21 66.3 2.52 116.7 3.84
24.4 1.24 67.2 2.55 118.3 3.87
25.5 1.26 68.1 2.58 119.9 3.90
26.6 1.26 69.1 2.61 121.5 3.93
27.6 1.32 70.0 2.64 123.2 3.96
28.7 1.35 70.9 2.67 124.9 3.98
29.7 1.38 71.9 2.70 126.6 4.01
30.7 1.41 72.8 2.73 128.4 4.04
31.7 1.44 73.8 2.76 130.3 4.07
32.7 1.47 74.8 2.76
33.7 1.50 75.8 2.82
34.7 1.53 76.7 2.85
35.7 1.56 77.7 2.88
36.7 1.59 78.7 2.91
37.6 1.62 79.7 2.93
38.6 1.65 80.7 2.96
39.6 1.67 81.7 2.99
40.5 1.70 82.7 3.02
41.4 1.73 83.6 3.05
42.4 1.76 84.6 3.08
43.3 1.79 85.7 3.11
44.3 1.82 86.7 3.13
45.2 1.85 87.8 3.16
46.1 1.88 88.9 3.19
47.0 1.91 90.1 3.22
48.0 1.94 91.1 3.25
48.9 1.97 92.2 3.28
99
TABLE 31 - OUTSIDE AIR TEMPERATURE INPUT VOLTAGE (MEASURED SIGNAL TO SHIELD AT THE SENSOR)