EasyManuals Logo

York YCAV0187 User Manual

York YCAV0187
310 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #274 background imageLoading...
Page #274 background image
274
JOHNSON CONTROLS
FORM 201.21-NM1 (1223)
MICRO PANEL
DEFAULT PROGRAMMABLE VALUES
To quickly program or reset most of the user program-
mable values to their default values, press PROGRAM,
6140, ENTER. The following message will then be
displayed, allowing a choice to reset the operating pa-
rameters to their default values.
YES or NO may be selected for XXX using the â—„ and
â–º (ARROW) keys to change the selection.
Following is a list of the operating parameters that will
be reset to their default values:
· Suction Pressure Cutout = 24.0 PSIG
· Low Ambient Air Temp Cutout = 25°F
· Leaving Chilled Liquid Temp Cutout = 36°F
· High Motor Current Limit = 100%
· Pulldown Current Limit = 100%
· Pulldown Current Limit Time = 0 Min.
· Suction Superheat Setpoint = 10°F
· Sound limit Setpoint = 0%
DEFAULTS SET PROG VALUES TO DEFAULT?
â—„ â–º XXX

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York YCAV0187 and is the answer not in the manual?

York YCAV0187 Specifications

General IconGeneral
BrandYork
ModelYCAV0187
CategoryChiller
LanguageEnglish

Related product manuals