MICRO PANEL
DEFAULT PROGRAMMABLE VALUES
To quickly program or reset most of the user program-
mable values to their default values, press PROGRAM,
6140, ENTER. The following message will then be
displayed, allowing a choice to reset the operating pa-
rameters to their default values.
YES or NO may be selected for XXX using the â—„ and
â–º (ARROW) keys to change the selection.
Following is a list of the operating parameters that will
be reset to their default values:
· Suction Pressure Cutout = 24.0 PSIG
· Low Ambient Air Temp Cutout = 25°F
· Leaving Chilled Liquid Temp Cutout = 36°F
· High Motor Current Limit = 100%
· Pulldown Current Limit = 100%
· Pulldown Current Limit Time = 0 Min.
· Suction Superheat Setpoint = 10°F
· Sound limit Setpoint = 0%
DEFAULTS SET PROG VALUES TO DEFAULT?
â—„ â–º XXX