76 Parameters
06.17 Drive status word 2 Drive status word 2.
This parameter is read-only.
0b0000
0b0000...0b1111 Drive st atus word 2. 1 = 1
06.18 Start inhibit status
word
Start inhibit status word. This word specifies the source of the
inhibiting signal that is preventing the drive from starting.
The conditions marked with an asterisk (*) only require that
the start command is cycled. In all other instances, the
inhibiting condition must be removed first.
See also parameter 06.16 Drive status word 1, bit 1.
This parameter is read-only.
0b0000
0b0000...0b1111 Start inhibit stat us word. 1 = 1
No. Name/Value Description Def/FbEq16
Bit Name Description
0 Identification run done 1 = Motor identification (ID) run has been performed
1 Magnetized 1 = The motor has been magnetized
2 Reserved 1 = Torque control mode active
3 Speed control 1 = Speed control mode active
4 Reserved
5 Safe reference active 1 = Asafe” reference is applied by functions such as
parameters 49.05 and 50.02
6 Last speed active 1 = Alast speed” reference is applied by functions such as
parameters 49.05 and 50.02
7...8 Reserved
9 Jogging active 1 = Jogging enable signal is on
10…12 Reserved
13 Start delay active 1 = Start delay (par. 21.22) active.
14…15 Reserved
Bit Name Description
0 Not ready run 1 = DC voltage is missing or drive has not been parametrized
correctly. Check the parameters in groups 95 and 99.
1 Ctrl location changed * 1 = Control location has changed
2 SSW inhibit 1 = Control program is keeping itself in inhibited state
3 Fault reset * 1 = A fault has been reset
4 Lost start enable 1 = Start enable signal missing
5 Lost run enable 1 = Run enable signal missing
6 Reserved
7 STO 1 = Safe torque off function active
8 Current calibration
ended
* 1 = Current calibration routine has finished
9 ID run ended * 1 = Motor identification run has finished
10 Reserved
11 Em Off1 1 = Emergency stop signal (mode off1)
12 Em Off2 1 = Emergency stop signal (mode off2)
13 Em Off3 1 = Emergency stop signal (mode off3)
14 Auto reset inhibit 1 = The autoreset function is inhibiting operation
15 Jogging active 1 = The jogging enable signal is inhibiting operation
ACQ80 FW.book Page 76 Thursday, February 14, 2019 11:33 AM

Table of Contents

Other manuals for ABB ACQ80-04

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACQ80-04 and is the answer not in the manual?

ABB ACQ80-04 Specifications

General IconGeneral
BrandABB
ModelACQ80-04
CategoryDC Drives
LanguageEnglish

Related product manuals