22 ACS 400 User’s Manual
400V Series
3~Input 380 - 480V
+/- 10% 50/60Hz
ACS401x
0043x 0053x 0063x 0093x 0113x 0163x 0203x 0253x 0303x 0413x
Frame Size Unit R1 R2 R3 R4
Nominal Ratings (See G)
Nominal Motor P
N
Normal Duty
Hp 3.05.07.510152025304050
Input Current I
1NND
A 6.2 8.3 11.1 14.8 21.5 29.0 35.0 41.0 56.0 68.0
Output Current I
2NND
A 6.6 8.8 11.6 15.3 23.0 30.0 38.0 44.0 59.0 72.0
Max. Output Current
I
2NNDmax
*
A 7.39.712.816.825.33342486579
Nominal Motor P
N
Heavy Duty
kW
Hp
2.0 3.0 5.0 7.5 10 15 20 25 30 40
Input current I
1N
A 4.7 6.2 8.3 11.1 14.8 21.5 29 35 41 56
Output Current I
2N
A 4.9 6.6 7.7 11.6 15.3 23 30 38 44 59
Max. Output current
I
2Nmax
*
A 7.49.913.217.4233445576688
Output Voltage V
2
V0 - V
1
Switching Frequency kHz 4 (Standard)
8 (Low Noise**)
Protection Limits
Overcurrent (peak) A 20.3 27.5 37 48 64 76 99 125 145 195
Overvoltage:
Running
Start Inhibit
VDC
VDC
842 (corresponds to 624 VAC input)
661 (in input voltage range 380-415 VAC)
765 (in input voltage range 440-480 VAC)
Undervoltage:
Running
Start Inhibit
VDC
VDC
333 (corresponds to 247 VAC input)
436 (in input voltage range 380-415 VAC)
505 (in input voltage range 440-480 VAC)
Overtemperature
°C / °F 95° C / 203° F (Heat Sink)
Max. Cable Length
f
SW
=4kHz****
m / ft. 100 / 320’ 200 / 640’ 200 / 640’ 200 / 640’
Max. wire sizes and screw torque of connectors
Power terminals
***
mm
2
/ Nm
/ lb/in.
10, AWG6 (stranded) /
Torque 1.3-1.5 Nm / 11 - 13 lb/in.
16, AWG4
(stranded) /
Torque
1.5-1.8 Nm /
13 - 16 lb/in.
35, AWG2 (stranded) /
Torque 3.2-3.7 Nm / 28
- 32 lb/in.
Control terminals mm
2
0.5 - 1.5 (AWG22...AWG16) / Torque 0.4 Nm
Line fuse 3~
****
A 101515203040506080100
Bussman Fuse Type KTK-10 KTK-15 KTK-15 KTK-20 KTK-30 JJS-40 JJS-50 JJS-60 JJS-80 JJS-100
Power losses
Power circuit W 90 120 170 230 330 450 560 660 900 1100
Control circuit W 6666666666
http://nicontrols.com