ACS 400 User’s Manual 21
T Specifications
Notes for the following tables are on page 23.
200 V Series
3~Input 208 - 240V
+/- 10% 50/60Hz
ACS401x
0004x 0005x 0006x 0009x 0011x 0016x 0020x 0030x 0041x
Frame Size Unit R1 R2 R3 R4
Nominal Ratings (See G & M)
Nominal motor P
N
Normal Duty
kW
Hp
2.2
3
4
5
5.5
7.5
7.5
10
11
15
15
20
18.5
25
22
30
30
40
Input Current I
1N
3~ A 10.0 15.7 22.7 29.0 43.4 55.8 70.3 82.7 107.2
Output Current I
2N
A 10.6 16.7 24.2 30.8 46.2 59.4 74.8 88 114
Max. Output Current
I
2Nmax
A 11.7 18.4 26.6 33.9 50.8 65.3 82.3 96.8 125.4
Nominal motor P
N
Heavy Duty
kW
Hp
1.5
2
2.2
3
4
5
5.5
7.5
7.5
10
11
15
15
20
18.5
25
22
30
Input current I
1NHD
3~ A 7.1 10.0 15.7 22.8 29.0 43.6 56.0 70.5 83.0
Output Current I
2NHD
A 7.5 10.6 16.7 24.2 30.8 46.2 59.4 74.8 88
Max. Output current
I
2NHDmax
A 11.3 15.9 25.1 36.3 46.2 69.3 89.1 112.2 132.0
Output Voltage U
2
V0 - U
1
Switching Frequency kHz 4 (standard)
8 (Low Noise)**
Protection Limits
Overcurrent (peak) A 31.4 44.3 69.8 101.2 128.7 142.3 196.0 279.8 367.8
Overvoltage:
Running
Start Inhibit
VDC
VDC
421 VDC (1.3*U
DC
Nominal @ 240 VAC input)
1.18 * U
DC
Nominal @ 240 VAC
Undervoltage:
Running
Start Inhibit
VDC
VDC
182 VDC (0.65 * U
DC
Nominal @ 208 VAC Input)
0.85 * U
DC
Nominal @ 208 VAC
Overtemperature
°C / °F95° C / 203° F (Heat Sink)
Max. Wire Sizes and Screw Torque of Connectors
Power Terminals
mm
2
/
Nm /
lb/in.
10, AWG6
(Stranded) /
Torque 1.3 -
1.5 Nm / 11 -
13 lb/in.
10, AWG6
(Stranded) /
Torque 1.3 -
1.5 Nm / 13 -
16 lb/in.
35, AWG2
(Stranded) /
Torque 3.2 -
3.7 Nm / 28 -
32 lb/in.
35, AWG2 (Stranded) /
Torque 3.2 - 3.7 Nm /
28 - 32 lb/in.
Control Terminals
mm
2
0.5 - 1.5 (AWG22...AWG16) / Torque 0.4 Nm
Line Fuse 3~ A 16 25 25 35 50 80 80 100 125
Bussmann Type
KTK-15 KTK-25 KTK-25 KTK-35 JJS-50 JJS-80 JJS-80
JJS-100 JJS-125
Power Losses
Power Circuit W 60 88 160 220 300 440 600 740 880
Control Circuit W 6 6 6 6 6 6 6 6 6