ACS 400 User’s Manual 53
Application Macros
Application Macros are preprogrammed parameter sets. They minimize the number of different
parameters to be set during start-up. The Factory Macro is the factory-set default macro.
Note! The Factory Macro is intended for applications where there is NO control panel available. If
using the Factory Macro with control panel, note that the parameters whose value depend
on digital input DI4 cannot be modified from the panel.
Parameter Values
Selecting an application macro with parameter 9902
APPLIC MACRO will set all other parameters
(except the group 99 Start-up Data parameters, the parameter lock 1602, the parameter save 1607
and groups 50 - 52 serial communication parameters) to their default values.
Default values of certain parameters depend on the selected macro. These are listed with the
description of each macro. Default values for other parameters are given in “ACS 400 Complete
Parameter List” on page 65.
Connection Examples
In the following connection examples please note:
• All the digital inputs are connected using negative (NPN) logic.