ACS 400 User’s Manual 49
ACS 400 Basic Parameters
The ACS 400 has a large number of parameters. Of these, only the so-called basic parameters are
initially visible.
Setting up only a few basic parameters is sufficient in applications where the preprogrammed
application macros of the ACS 400 can provide all desired functionality. For a full description of the
programmable features provided by the ACS 400, see “ACS 400 Complete Parameter List” on
page 65.
The following table lists the basic parameters.
S = Parameters can be modified only when the drive is stopped.
Code Name User S
Group 99
START-UP DATA
9901 LANGUAGE
Language selection.
9902 APPLIC MACRO
Selects application macro. Sets parameter values to their default values. Refer to
CROSSREF for a detailed description of each macro.
0 =
FACTORY
1 = ABB STANDARD
2 = 3-WIRE
3 = ALTERNATE
4 = MOTOR POT
5 = HAND/AUTO
6 = PID CONTROL
7 = PREMAGN
8 = PFC CONTROL
Default value: 0 (FACTORY MACRO)
á
9905 MOTOR NOM VOLT
Nominal motor voltage from motor name plate. Range of this parameter depends on the
type of the ACS 400.
Default value: 400 V unit: 460 V
200 V unit: 230 V
á
9906 MOTOR NOM CURR
Nominal motor current from motor name plate. Values for this parameter range from
0.5* I
N
- 1.5* I
N
, where I
N
is nominal current of the ACS 400.
Default value: I
N
á
9907 MOTOR NOM FREQ
Nominal motor frequency from motor name plate.
Range: 0 - 250 Hz
Default value: 60 Hz
á
0 = ENGLISH 4 = SPANISH 8 = DANISH 12 = (reserved)
1=
ENGLISH (AM)5 = PORTUGUESE 9 = FINNISH
2 = GERMAN 6 = DUTCH 10 = SWEDISH
3 = ITALIAN 7 = FRENCH 11 = RUSSIAN