ACS 400 User’s Manual 65
ACS 400 Complete Parameter List
Initially, only the so called basic parameters (shaded grey in Table 7) are visible. Use the
appropriate menu function of the control panel to make the full parameter set visible.
S = Parameters can be modified only when the drive is stopped.
M = Default value depends on the selected macro (*).
Table 7 Full parameter set.
Code Name Range Resolution Default User S M
Group 99
START-UP DATA
9901 LANGUAGE 0 - 11 1 0 (ENGLISH)
9902 APPLIC MACRO 0 - 13 1 0 (FACTORY)
á
9905 MOTOR NOM VOLT 200, 208, 220, 230, 240,
380, 400, 415, 440, 460,
480 V
- 230 V
460 V
á
9906 MOTOR NOM CURR 0.5*I
N
- 1.5*I
N
0.1 A 1.0*I
N
á
9907 MOTOR NOM FREQ 0 - 250 Hz 1 Hz 60 Hz
á
9908 MOTOR NOM SPEED 0 - 3600 rpm 1 rpm 1750 rpm
á
9909 MOTOR NOM POWER 0.1 - 134 HP 0.1 HP 3 - 50 HP
Size Dependent
á
9910 MOTOR COS PHI
(
MOTOR POWER FACTOR)
0.50 - 0.99 0.01 0.83
á
Group 01
OPERATING DATA
0102
SPEED 0 - 9999 rpm 1 rpm -
0103
OUTPUT FREQ 0 - 250 Hz 0.1 Hz -
0104
CURRENT - 0.1 A -
0105
TORQUE -100...100 % 0.1 % -
0106
POWER - 0.1 kW -
0107
DC BUS VOLTAGE 0 - 999.9 V 0.1 V -
0109
OUTPUT VOLTAGE 0 - 480 V 0.1 V -
0110
ACS400 TEMP 0 - 300 °F0.1 °F-
0111
EXTERNAL REF 1 0 - 250 Hz 0.1 Hz -
0112
EXTERNAL REF 2 0 - 100 % 0.1 % -
0113
CTRL LOCATION 0 - 2 1 -
0114
RUN TIME (R) 0 - 9999 h 1 h -
0115 kWh
COUNTER (R) 0 - 9999 kWh 1 kWh -
0116
APPL BLK OUTPUT 0 - 100 % 0.1 % -
0117
DI1-DI4 STATUS 0000 - 1111
(0 - 15 decimal)
1-
0118
AI1 0 - 100 % 0.1 % -
0119
AI2 0 - 100 % 0.1 % -
0121
DI5 & RELAYS 0000 - 0111
(0 - 7 decimal)
1-
0122
AO 0 - 20 mA 0.1 mA -
0124
ACTUAL VALUE 1 0 - 100 % 0.1 % -
http://nicontrols.com