16. Troubleshooting
16.1. Error messages
Base Unit not responding, communication corrupted or wrong
slave address
When the HMI is not able to communicate with the Base Unit, the following
information appears on the LCD:
A051367 2
Fig. 16.1.-1 HMI is not able to communicate with the Base Unit
Solution:
Check that the Base Unit is powered and regularly working. Look at the status LED
on the connector panel (Slot X7).
The LED close to the analog inputs is related to the watchdog. When the Base Units
is working this LED is on with a weak light.
The other LED is related to the communication with the HMI. When the
communication is properly working, this LED is blinking. When the communication
is not working, the LED can be either ON or OFF. It depends on when the
communication is interrupted.
Check that the connection cable between the HMI and the Base Unit is inserted both
in the HMI and in the Base Unit (Base Unit connector X73 and HMI connector
X20) and properly tighten.
Check the slave address of the connected Base Unit to be polled. The address is
configured in the application file. If you do not know you can enter the following
page by pressing ENTER.
Multifunction Protection and Switchgear Control Unit
Operator's manual
REF 542plusREF 542plus
1MRS755869

Table of Contents

Other manuals for ABB REF 542plus

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REF 542plus and is the answer not in the manual?

ABB REF 542plus Specifications

General IconGeneral
BrandABB
ModelREF 542plus
CategoryControl Unit
LanguageEnglish

Related product manuals