EasyManuals Logo
Home>ABB>Protection Device>RELION RET670

ABB RELION RET670 User Manual

ABB RELION RET670
1016 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #545 background imageLoading...
Page #545 background image
calculate the value of ZN as V/(√3 · 3I
0
) Typically
, the minimum ZNPol (3 · zero
sequence source) is set. The setting is in primary ohms.
When the dual polarizing method is used, it is important that the setting Pickupx or the
product 3I
0
· ZNpol is not greater than 3V
0
. If so, there is a risk for incorrect operation
for faults in the reverse direction.
IPolMin: is the minimum ground-fault current accepted for directional evaluation. For
smaller currents than this value, the operation will be blocked. A typical setting is
5-10% of IB.
VPolMin: Minimum polarization (reference) polarizing voltage for the directional
function, given in % of VBase/√3.
IDirPU: Operate residual current release level in % of IB for directional comparison
scheme. The setting is given in % of IB and must be set below the lowest INx> setting,
set for the directional measurement. The output signals, PUFW and PUREV can be
used in a teleprotection scheme. The appropriate signal should be configured to the
communication scheme block.
9.4.3.2 2nd harmonic restrain
M15282-90 v6
If a power transformer is energized there is a risk that the current transformer core will
saturate during part of the period, resulting in a transformer inrush current. This will
give a declining residual current in the network, as the inrush current is deviating
between the phases. There is a risk that the residual overcurrent function will give an
unwanted trip. The inrush current has a relatively large ratio of 2nd harmonic
component. This component can be used to create a restrain signal to prevent this
unwanted function.
At current transformer saturation a false residual current can be measured by the
protection. Here the 2
nd
harmonic restrain can prevent unwanted operation as well.
2ndHarmStab: The rate of 2nd harmonic current content for activation of the 2nd
harmonic restrain signal. The setting is given in % of the fundamental frequency
residual current.
9.4.3.3 Parallel transformer inrush current logic
M15282-97 v6
In case of parallel transformers there is a risk of sympathetic inrush current. If one of
the transformers is in operation, and the parallel transformer is switched in, the
asymmetric inrush current of the switched-in transformer will cause partial saturation
of the transformer already in service. This is called transferred saturation. The 2
nd
harmonic of the inrush currents of the two transformers will be in phase opposition.
The summation of the two currents will thus give a small 2
nd
harmonic current. The
1MRK 504 163-UUS A Section 9
Current protection
Transformer protection RET670 2.2 ANSI 539
Application manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RELION RET670 and is the answer not in the manual?

ABB RELION RET670 Specifications

General IconGeneral
BrandABB
ModelRELION RET670
CategoryProtection Device
LanguageEnglish

Related product manuals