Table 55: Possible cause values from XLNPROXY
Cause No Cause Description Conditions
8 Blocked-by-Mode The BEH input is 5.
2 Blocked-by-switching-hierarchy The LOC input indicates that only local commands are
allowed for the breaker IED function.
-24 Blocked-for-open-cmd The BLKOPN is active indicating that the switch is
blocked for open commands.
-25 Blocked-for-close-cmd The BLKCLS is active indicating that the switch is
blocked for close commands.
9 Blocked-by-process If the Blk input is connected and active indicating that the
switch is dynamically blocked. Or if the OPCAP input is
connected, it indicates that the operation capability of the
switch is not enough to perform the command.
5 Position-reached Switch is already in the intended position.
-31 Switch-not-start-moving Switch did not start moving within tStartMove.
-32 Persistent-intermediate-state The switch stopped in intermediate state for longer than
tIntermediate.
-33 Switch-returned-to-init-pos Switch returned to the initial position.
-34 Switch-in-bad-state Switch is in a bad position.
-35 Not-expected-final-position Switch did not reach the expected final position.
The OPCAP input and output are used for the CBOpCap data of a
XCBR respectively SwOpCap for a XSWI. The interpretation for the
command following is controlled through the setting SwitchType.
15.2.1.5 Reservation function (QCRSV and RESIN)
M16609-3 v4
The purpose of the reservation function is primarily to transfer interlocking
information between IEDs in a safe way and to prevent double operation in a bay,
switchyard part, or complete substation.
For interlocking evaluation in a substation, the position information from switching
devices, such as circuit breakers, disconnectors and
grounding switches can be required
from the same bay or from several other bays. When information is needed from other
bays, it is exchanged over the station bus between the distributed IEDs. The problem
that arises, even at a high speed of communication, is a space of time during which the
information about the position of the switching devices are uncertain. The interlocking
function uses this information for evaluation, which means that also the interlocking
conditions are uncertain.
To ensure that the interlocking information is correct at the time of operation, a unique
reservation method is available in the IEDs. With this reservation method, the bay that
Section 15 1MRK 504 163-UUS A
Control
708 Transformer protection RET670 2.2 ANSI
Application manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RELION RET670 and is the answer not in the manual?

ABB RELION RET670 Specifications

General IconGeneral
BrandABB
ModelRELION RET670
CategoryProtection Device
LanguageEnglish

Related product manuals