Section 22 Remote communication
22.1 Binary signal transfer
IP12423-1 v2
22.1.1
Identification
M14849-1 v3
Function description IEC 61850 identification IEC 60617
identification
ANSI/IEEE C37.2
device number
Binary signal transfer,
receive
BinSignRec1_1
BinSignRec1_2
BinSignReceive2
- -
Binary signal transfer, 2Mbit
receive
BinSigRec1_12M
BinSigRec1_22M
- -
Binary signal transfer,
transmit
BinSignTrans1_1
BinSignTrans1_2
BinSignTransm2
- -
Binary signal transfer, 2Mbit
transmit
BinSigTran1_12M
BinSigTran1_22M
- -
22.1.2 Application
IP16245-1 v1
M12844-3 v4
The IEDs can be equipped with communication devices for line differential
communication (not applicable for RER670) and/or communication of binary signals
between IEDs. The same communication hardware is used for both purposes.
Sending of binary signals between two IEDs is used in teleprotection schemes and for
direct transfer trips. In addition to this, there are application possibilities, for example,
blocking/enabling functionality in the remote substation, changing setting group in the
remote IED depending on the switching situation in the local substation and so on.
If equipped with a 64kbit/s LDCM module, the IED can be configured to send either
192 binary signals or 3 analog and 8 binary signals to a remote IED. If equipped with a
2Mbps LDCM module, the IED can send 9 analog channels and 192 binary channels to
a remote IED.
Link forwarding
GUID-DD3CF47C-A202-4416-954A-EFC0F8BEBCB7 v1
If it is not possible to have a communication link between each station, the solution has
been to set the protection up in a slave-master
-slave configuration. This means that in
Figure
425, only IED-B has access to all currents and, therefore, this is the only place
1MRK 504 163-UUS A Section 22
Remote communication
Transformer protection RET670 2.2 ANSI 951
Application manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RELION RET670 and is the answer not in the manual?

ABB RELION RET670 Specifications

General IconGeneral
BrandABB
ModelRELION RET670
CategoryProtection Device
LanguageEnglish

Related product manuals