ANSI07000112-3-en.vsd
PSTO
CMDPOS12
IPOS1
NAM_POS1
NAM_POS2
IPOS2
CMDPOS21
Disabled
Enabled
VSGAPC
SMBRREC_79
ON
OFF
SETON
INTONE
INV
OUT
INPUT
ANSI07000112 V3 EN-US
Figure 378: Control of Autorecloser from local HMI through Selector mini switch
VSGAPC is also provided with IEC 61850 communication so it can be controlled from
SA system as well.
15.6.3 Setting guidelines
SEMOD158807-4 v4
Selector mini switch (VSGAPC) function can generate pulsed or steady commands (by
setting the Mode parameter). When pulsed commands are generated, the length of the
pulse can be set using the tPulse parameter. Also, being accessible on the single line
diagram (SLD), this function block has two control modes (settable through CtlModel):
Dir Norm and SBO Enh.
15.7 Generic communication function for Double Point
indication DPGAPC
SEMOD55384-1 v4
15.7.1 Identification
GUID-E16EA78F-6DF9-4B37-A92D-5C09827E2297 v3
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Generic communication function for
Double Point indication
DPGAPC - -
15.7.2 Application
SEMOD55391-5 v8
Generic communication function for Double Point indication (DPGAPC) function
block is used to send double point position indication to other systems, equipment or
functions in the substation through IEC 61850-8-1 or other communication protocols.
Section 15 1MRK 504 163-UUS A
Control
804 Transformer protection RET670 2.2 ANSI
Application manual