SpChAlmTime: Time delay for spring char
ging time alarm.
tDGasPresAlm: Time delay for gas pressure alarm.
tDGasPresLO: Time delay for gas pressure lockout.
DirCoef: Directional coefficient for circuit breaker life calculation.
RatedOperCurr: Rated operating current of the circuit breaker.
RatedFltCurr: Rated fault current of the circuit breaker.
OperNoRated: Number of operations possible at rated current.
OperNoFault: Number of operations possible at rated fault current.
CBLifeAlmLevel: Alarm level for circuit breaker remaining life.
AccSelCal: Selection between the method of calculation of accumulated energy.
OperTimeDelay: Time delay between change of status of trip output and start of main
contact separation.
18.5 Event function EVENT
IP14590-1 v2
18.5.1 Identification
SEMOD167950-2 v2
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Event function EVENT
S00946 V1 EN-US
-
18.5.2 Application
M12805-6 v11
When using a Substation Automation system with LON or SPA communication, time-
tagged events can be sent at change or cyclically from the IED to the station level.
These events are created from any available signal in the IED that is connected to the
Event function (EVENT).
The EVENT function block is used for remote
communication.
Analog, integer and double indication values are also transferred through the EVENT
function.
Section 18 1MRK 504 163-UUS A
Monitoring
884 Transformer protection RET670 2.2 ANSI
Application manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RELION RET670 and is the answer not in the manual?

ABB RELION RET670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
Communication ProtocolsIEC 61850, IEC 60870-5-103, DNP3
Operating Temperature Range-25°C to +55°C
MountingRack Mounting
Input Voltage100-240 V AC
Protection FunctionsOvercurrent Protection
EnclosureIP20