The sum of the numbers in column “Value when activated” when all INx (where
1≤x≤16) are active that is=1; is 65535. 65535 is the highest boolean value that can be
converted to an integer by the B16I function block.
17.9 Boolean to integer conversion with logical node
representation, 16 bit BTIGAPC
SEMOD175753-1 v4
17.9.1
Identification
SEMOD175757-2 v5
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Boolean to integer conversion with
logical node representation, 16 bit
BTIGAPC - -
17.9.2 Application
SEMOD175849-4 v6
Boolean to integer conversion with logical node representation, 16 bit (BTIGAPC) is
used to transform a set of 16 binary (logical) signals into an integer. BTIGAPC has a
logical node mapping in IEC 61850.
The BTIGAPC function will transfer a combination of up to 16 binary inputs INx
where 1≤
x≤16 to an integer. Each INx represents a value according to the table below
from 0 to 32768. This follows the general formula: INx = 2
x-1
where 1≤x≤16. The sum
of all the values on the activated INx will be available on the output OUT as a sum of
the values of all the inputs INx that are activated. OUT is an integer. When all INx
where 1≤x≤16 are activated that is = Boolean 1 it corresponds to that integer 65535 is
available on the output OUT. BTIGAPC function is designed for receiving up to 16
booleans input locally. If the BLOCK input is activated, it will freeze the output at the
last value.
Values of each of the different OUTx from function block BTIGAPC for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output
OUT on the function block BTIGAPC.
Name of input Type Default Description Value when
activated
Value when
deactivated
IN1 BOOLEAN 0 Input 1 1 0
IN2 BOOLEAN 0 Input 2 2 0
IN3 BOOLEAN 0 Input 3 4 0
Table continues on next page
1MRK 504 163-UUS A Section 17
Logic
Transformer protection RET670 2.2 ANSI 853
Application manual