The connections are similar in all SESRSYN functions, apart from the breaker position
indications. The physical analog connections of voltages and the connection to the IED
and SESRSYN (25) function blocks must be carefully checked in PCM600. In all
SESRSYN functions the connections and configurations must abide by the following
rules: Normally apparatus position is connected with contacts showing both open (b-
type) and closed positions (a-type).
W
A1_QA1:
BUS1_OP/CL = Position of TIE_QA1 breaker and belonging disconnectors
BUS2_OP/CL = Position of WA2_QA1 breaker and belonging disconnectors
LINE1_OP/CL = Position of LINE1_QB9 disconnector
LINE2_OP/CL = Position of LINE2_QB9 disconnector
VB1OK/FF = Supervision of WA1_MCB fuse
VB2OK/FF = Supervision of WA2_MCB fuse
VL1OK/FF = Supervision of LINE1_MCB fuse
VL2OK/FF = Supervision of LINE2_MCB fuse
Setting CBConfig = 1 1/2 bus CB
TIE_QA1:
BUS1_OP/CL = Position of WA1_QA1 breaker and belonging disconnectors
BUS2_OP/CL = Position of WA2_QA1 breaker and belonging disconnectors
LINE1_OP/CL = Position of LINE1_QB9 disconnector
LINE2_OP/CL = Position of LINE2_QB9 disconnector
VB1OK/FF = Supervision of WA1_MCB fuse
VB2OK/FF = Supervision of WA2_MCB fuse
VL1OK/FF = Supervision of LINE1_MCB fuse
VL2OK/FF = Supervision of LINE2_MCB fuse
Setting CBConfig = Tie CB
WA2_QA1:
BUS1_OP/CL = Position of WA1_QA1 breaker and belonging disconnectors
BUS2_OP/CL = Position of TIE_QA1 breaker and belonging disconnectors
LINE1_OP/CL = Position of LINE1_QB9 disconnector
LINE2_OP/CL = Position of LINE2_QB9 disconnector
VB1OK/FF = Supervision of WA1_MCB fuse
VB2OK/FF = Supervision of WA2_MCB fuse
VL1OK/FF = Supervision of LINE1_MCB fuse
VL2OK/FF = Supervision of LINE2_MCB fuse
Setting CBConfig = 1 1/2 bus alt. CB
If only two SESRSYN functions are provided in the same IED, the connections and
settings are according to the SESRSYN functions for WA1_QA1 and TIE_QA1.
1MRK 504 163-UUS A Section 15
Control
Transformer protection RET670 2.2 ANSI 691
Application manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RELION RET670 and is the answer not in the manual?

ABB RELION RET670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
Communication ProtocolsIEC 61850, IEC 60870-5-103, DNP3
Operating Temperature Range-25°C to +55°C
MountingRack Mounting
Input Voltage100-240 V AC
Protection FunctionsOvercurrent Protection
EnclosureIP20

Related product manuals