40 Rockwell Automation Publication 750-PC108A-EN-P - April 2021
PowerFlex 755T Drives Configured to Order Program Product Information
Barrel Lug to Drive Input Busbar Connection Hardware
To determine if you must make a connection using this hardware during installation, see Electrical Connections Made to Each Configured Bay During Installation on page 17. This hardware is used in the drive input bay to
make the power connection from some types of configured input bay to the drive input bay. The cable length for this connection is 2.5…3 m (8…10 ft).
Figure 40 - Barrel Lug Connection to Drive Input Busbars
Drive Main Control Board Connection Hardware
To determine if you must make a connection using this hardware during installation, see Electrical Connections Made to Each Configured Bay During Installation on page 17. This hardware is used to connect the configured
input bay drive disable push button to the main control board in the control pod in the drive input bay.
Figure 41 - Drive Disable Push Button to Main Control Board Connection Hardware
22-Series I/O Option Module Connection Hardware
To determine if you must make a connection using this hardware during installation, see Electrical Connections Made to Each Configured Bay During Installation on page 17. This hardware is used to connect various devices
in the configured input bay to the 22-Series I/O Option Module in the control pod in the drive input bay. For a full list of all devices that are connected to the module with these connections, see the electrical schematic that
came with your product.
Item Name Description
1 TB1 Drive disable push button male connector, has two 18 AWG wires connected. Must connect to item 2 during installation.
2 TB1 Input/output terminal block female connector
Figure 42 - 22-Series I/O Option Module Connection Hardware Item Identification Description
1 TB2 I/O module output connector male
2TB2
I/O module output connector female. Must connect to item 1
during installation.
3 TB1 I/O module input connector male
4TB1
I/O module input connector female. Must connect to item 3
during installation.
M10
40 mm
100 N•m (885 lb•in)